p.537conference rooms, kitchen areas in office spaces, and copy rooms. Plug-in strips and other plug-in devices shall not be used to comply with the requirements of this section.
p.537Controlled receptacles shall meet the following requirements, as applicable:
p.5371. Install a control capable of automatically shutting OFF the controlled receptacles when the space is typically unoccupied, either at the receptacle or circuit level. When an automatic time switch control is installed it shall incorporate an override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override is initiated and an automatic holiday “shut-OFF” feature that turns OFF all loads for at least 24 hours and then resumes the normally scheduled operation. Countdown timer switches shall not be used to comply with the automatic time switch control requirements; and
p.5372. Install at least one controlled receptacle within 6 feet from each uncontrolled receptacle, or install a multiple receptacle outlet with at least one controlled and one uncontrolled receptacle. Where receptacles are installed in modular furniture in open office areas, at least one controlled receptacle shall be installed at each workstation; and
p.5373. Provide a permanent marking for controlled receptacles or circuits to differentiate them from uncontrolled receptacles or circuits; and
p.537A. Receptacles specifically for refrigerators and water dispensers in kitchen areas.
p.537B. Receptacles located a minimum of six feet above the floor that are specifically for clocks.
p.537C. Receptacles for network copiers, fax machines, A/V and data equipment other than personal
p.537computers in copy rooms.
p.537D. Receptacles on circuits rated more than 20 amperes.
p.537E. Receptacles connected to an uninterruptible power supply (UPS) that are intended to be in
p.537continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.
p.537(e) Demand responsive controls and equipment. See Section 110.12 for requirements for demand
p.537responsive controls and equipment, including demand responsive controls for controlled receptacles.
p.537SECTION 160.6 – MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEM