RA3.6.2 Verified Pipe Insulation for Single Dwelling Systems

p.4252025 Residential Appendices RA3.6.2 Verified Pipe Insulation for Single Dwelling Systems

p.425The ECC-rater shall verify that all domestic hot water piping meet the insulation requirements specified in §150.0(j). The rater shall visually verify the following:

p.425(a) All domestic hot water piping shall be insulated as specified in Section 609.12 of the California

p.425Plumbing Code. (b) Pipe insulation shall fit tightly to the pipe and all elbows and tees shall be fully insulated. No

p.425piping should be visible due to insulation voids with the exception of the last segment of piping that penetrates walls and delivers hot water to the sink, appliance, etc. (c) All piping below grade must be installed in a waterproof and non-crushable casing or sleeve

p.425that allows for installation, removal and replacement of the enclosed pipe and insulation. The internal cross-section or diameter of the casing or sleeve shall be large enough to allow for insulation of the hot water piping. (d) Pipe insulation may be omitted where hot water distribution piping is buried within attic,

p.425crawlspace or wall insulation, as described below: 1. In attics and crawlspaces the insulation shall completely surround the pipe with at least 1 inch of insulation and the pipe shall be completely covered with at least 4 inches of insulation further away from the conditioned space. 2. In walls, the insulation must completely surround the pipe with at least 1 inch of insulation.

p.425RA3.6.3 Verified Pipe Insulation for Central Systems

p.425For central systems with hot water piping serving multiple dwelling units, the heating plant and recirculation system piping insulation installation quality shall be field verified by a ECC-rater. The ECC-rater shall inspect the heating plant and horizontal supply header and return piping in accordance with the requirements in Title 24 Part 6 section 170.2(d). The rater shall use a sampling approach that one in seven DHW recirculation pipe risers and associated branches be inspected to verify the pipe insulation meet with the following requirements:

p.425(a) All piping for multifamily domestic hot water systems shall be insulated to the thickness specified

p.425in Table 160.4-A, including the first 8 feet of inlet cold water piping to the heating plant. Insulation on the piping and appurtenances shall be continuous.

p.425(b) All appurtenances at the heating plant, from a heating source to storage tank(s), or in between

p.425storage tanks and storage water heaters, and recirculation supply and return loop shall meet the following:

p.4251. Insulation to be flush with pipe insulation or have minimum of one inch if appurtenance is bulkier.

p.4252. Removable and re-installable for maintenance or replacement.

p.4253. Pipe supports, hangers, and clamps shall be attached on the outside of rigid pipe insulation.

p.425(c) All pipe insulation seams shall be sealed along the length of the pipe and between adjacent

p.425sections of insulation material.

p.425(d) Insulation for pipe elbows shall be mitered, and insulation for tees shall be notched. Alternatively,

p.425tees and elbows may be pre-formed, or site fabricated with PVC covers.

p.425Appendix RA3– Residential Field Verification and Diagnostic Test Protocols