p.5622025 Nonresidential Appendices For buildings with up to seven multi-zone occupant sensors, all occupant sensors shall be tested. For buildings with more than seven multi-zone occupant sensors, sampling may be done on the space to choose up seven multi-zone occupant sensors from the space and all seven multi-zone occupant sensors shall be tested.
p.562NA7.6.2.3 Occupant Sensing Lighting Controls Functional Testing
p.562This requirement applies to areas where occupant sensing controls are required to comply with Section 130.1(c) with the exception of Section 130.1(c)6D.
p.562For each sensor to be tested do the following:
p.562(a) Unoccupied Test. Simulate an unoccupied condition in the controlled space.
p.562Verify and document the following:
p.5621. The occupant sensing control turn the controlled lighting off or partially-off in 20 minutes or less from the start of an unoccupied condition. In addition:
p.562a. For partial-on occupant sensing controls, occupant sensing controls and
p.562vacancy sensing controls, the controlled lighting is turned off in unoccupied condition.
p.562b. In the partially off state, partial off occupant sensing controls automatically
p.562reduce lighting power by at least 50 percent, or automatically reduce in one of the following:
p.562i. For warehouses with metal halide or high pressure sodium lighting,
p.562reduce lighting power by at least 40 percent;
p.562ii. For aisle ways and open areas in warehouses in which the installed
p.562lighting power is 80 percent or less of the value allowed under the Area Category Method, reduce lighting power by at least 40 percent;
p.562iii. For corridors and stairwells that provide access to guestrooms and
p.562dwelling units of high-rise residential buildings and hotel/motels in which the installed lighting power is 80 percent or less of the valued allowed under the Area Category Method, reduce lighting power by at least 40 percent.
p.562c. For occupant sensing controls in parking garages, parking areas, and
p.562loading and unloading areas, the control has at least one control step between 20 to 50 percent of the design lighting power, or the controls has at least one control step between 20 to 60 percent of the design lighting power - for the controls serving metal halide luminaires with a lamp plus ballast mean system efficacy of 75 lumens per watt. In the partially off state, partial off occupant sensing controls automatically reduce lighting power by one control step.
p.562(b) Occupied Test. Simulate an occupied condition in the controlled space. Verify and
p.562document the following:
p.5621. Status indicator or annunciator operates correctly.
p.5622. Immediately upon an occupied condition:
p.562Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes