p.5612025 Nonresidential Appendices has more than three (3) steps between on and off, testing three (3) control steps between on and off is sufficient to demonstrate compliance. If the control system has zero (0) steps between on and off, the partial daylight test is not necessary. For stepped switching control systems, steps in a controlled zone are achieved by turning some luminaires or groups of luminaires on or off without any steps between on and off.
p.561For each control stage that is tested in this step, the control stages with lower setpoints than the stage tested are left ON and those stages of control with higher setpoints are dimmed or controlled off. Simulate or provide conditions so that each control stage turns on and off or dims. Verify and document the following for each control stage:
p.5611. Measure that the combined daylight and controlled electric lighting illuminance at the Reference Location is no less than the reference illuminance measured at this location during the No Daylight Test.
p.5612. Verify that the combined daylight and controlled electric lighting illuminance at the Reference Location is no greater than 150 percent of the reference illuminance.
p.5613. Light output is stable with no visible flicker. (Note: only luminaires in daylit zones are affected by daylight control)
p.5614. The control stage shall not cycle on and off or cycle between dim and undimmed while daylight illuminance remains constant.
p.561NA7.6.2 Shut-off Controls Acceptance Tests
p.561NA7.6.2.1 Occupant Sensing Lighting Controls Construction Inspection
p.561Prior to Functional testing, verify and document the following:
p.561(a) The occupant sensing lighting controls are shown on plan documents and are
p.561installed.
p.561(b) Occupant sensing lighting control is installed per manufacturer’s instructions to
p.561minimize false triggering- such as to install an occupancy sensor away from HVAC diffusers to avoid probable false triggering.
p.561NA7.6.2.2 Occupant Sensing Lighting Controls Functional Testing – Sampling
p.561For buildings with up to seven (7) occupant sensors, all occupant sensors shall be tested. For buildings with more than seven (7) occupant sensors, sampling may be done on spaces with similar sensors and space geometries; sampling shall include a minimum of 1 occupant sensor for each group of up to 7 additional occupant sensors. If the first occupant sensor in the sample group passes the acceptance test, the remaining building spaces in the sample group also pass. If the first occupant sensor in the sample group fails the acceptance test, the rest of the occupant sensors in that group must be tested. If any tested occupant sensor fails it shall be repaired, replaced, or adjusted until it passes the test.