NA7.6.1.5 Stepped Switching or Stepped Dimming Control Systems Functional Testing

p.5592025 Nonresidential Appendices (d) Partial Daylight Test. Simulate or provide daylight conditions where illuminance

p.5602025 Nonresidential Appendices (a) Reference Location. Identify the minimum daylight location in the controlled zone

p.559provided only by daylight only at the Reference Location is between 60 and 95 percent of Reference Illuminance measured during the No Daylight Test. Verify and document the following:

p.560(Reference Location) for each daylit zone type (skylit, primary sidelit, and secondary sidelit) in the space. This can be identified using either the illuminance method or the distance method and will be used for illuminance measurements in subsequent tests. For parking garages, the reference location should always be the farthest edge of the secondary sidelit daylit zone away from the opening or glazing.

p.5591. Measure that the combined daylight and controlled electric lighting illuminance at the Reference Location is no less than the reference illuminance measured at this location during the No Daylight Test.

p.560Illuminance Method

p.5592. Verify that the combined daylight and controlled electric lighting illuminance at the Reference Location is no greater than 150 percent of the reference illuminance.

p.560The Reference Location is the task location with lowest daylight illuminance in the zone illuminated by controlled luminaires.

p.5593. Light output is stable with no visible flicker.

p.560Turn off controlled lighting and measure daylight illuminance within zones illuminated by controlled luminaires. (Note: turn the controlled lighting back on before proceeding to the No Daylight Test)

p.559(Note: only luminaires in daylit zones are affected by daylight control)

p.559(e) Alternate Partial Daylight Test. When outdoor horizontal illuminance is at least 4,000 fc and where illuminance from daylight only at the Reference Location (Partial Daylight Illuminance) is no greater than 80 percent of Reference Illuminance measured at this location during the No Daylight Test. Measure the outdoor horizontal illuminance level and the daylight illuminance level, and do not proceed until the illuminance criteria are met.

p.560Distance Method

p.560The Reference Location is the task location within the zone illuminated by controlled luminaires that is farthest away from daylight sources.

p.560(b) No daylight test. Simulate or provide conditions without daylight. Verify and

p.560document the following:

p.559Verify and document the following:

p.5601. Document the reference illuminance, which is the electric lighting illuminance level at the Reference Location.

p.5591. Measure the Partial Daylight Illuminance at the Reference Location. This can be measured by turning the electric lighting off. (Turn the electric lighting back on before proceeding to next step.)

p.5602. Daylight responsive control system turns on all stages of controlled lighting to full light output unless it has been documented, such as in design documents, that dimming luminaires have been intentionally tuned to less than full light output. 6.4.

p.5592. Measure the combined daylight and controlled electric lighting at the Reference Location.

p.5593. This alternate partial daylight test is passed if the measured illuminance value (from Step 2) is no less than the Reference Illuminance measured at this location during the no daylight test and no greater than Partial Daylight Combined Illuminance Maximum (PDCIM).

p.5603. Light output is stable with no visible flicker.

p.560(c) Full daylight test. Simulate or provide bright conditions where the daylight

p.560illuminance is greater than 150 percent of the reference illuminance (measured during the No Daylight Test). Alternatively, provide simulated bright conditions by shining a bright light into the daylight sensor. Verify and document the following:

p.559In other words, the measured value must be within the following range in order to pass this test.

p.5601. When daylight illuminance is greater than 150 percent of the design illuminance, lighting power reduction is at least 90 percent under fully dimmed conditions for non-parking garage locations. For parking garages, the lighting power reduction is 100 percent under fully dimmed conditions.

p.559Reference Illuminance (from the no daylight test) ≤ measured illuminance value (from Step 2) ≤ PDCIM,

p.559where PDCIM = Reference Illuminance (from the no daylight test) + 0.40 x Daylight Illuminance (from Step 1).

p.5602. RESERVED

p.5594. Light output is stable with no visible flicker.

p.5603. Only luminaires in daylit zones are affected by daylight control. If the daylighting control system controls luminaires outside of the daylight zones including those behind obstructions, the control system is not compliant.

p.5595. Only luminaires in daylit zones are affected by daylight control.

p.559NA7.6.1.5 Stepped Switching or Stepped Dimming Control Systems Functional Testing

p.560(d) Partial daylight test. If the control system has one (1) to three (3) steps of control

p.559Stepped switching or stepped dimming control systems provide no more than 10 discrete steps of control of light output.

p.560between on and off, test all control steps between on and off. If the control system