NA7.6.2.4 Multi-Zone Occupant Sensing Lighting Controls Functional Testing

p.5632025 Nonresidential Appendices a. The occupant sensing control or partial off occupant sensing control

p.563turns on controlled lighting; or

p.563b. The vacancy sensing control indicate a space is occupied and the

p.563controlled lighting can be turned on manually; or

p.563c. The partial-on occupant sensing control automatically turns on the

p.563controlled lighting at between 50 to 70 percent of controlled lighting power. After the partial-on stage, manual switches can be activated to turn on the controlled lighting at full controlled lighting power.

p.563NA7.6.2.4 Multi-Zone Occupant Sensing Lighting Controls Functional Testing

p.563This requirement applies to areas where multi-zone occupant sensing controls are required to comply with Section 130.1(c)6D for offices larger than 250 square feet.

p.563(a) Occupied Control Zone Test. Simulate an occupied condition in the control zone

p.563controlled by the occupant sensor. Verify and document the following:

p.5631. Simulate an occupancy in a control zone. Immediately upon occupancy of the control zone, the occupant sensors turn on controlled lighting.

p.5632. Measure the illuminance at a location in the control zone where the light output is from the controlled lighting at full light output.

p.5633. Signal sensitivity is adequate to achieve desired control.

p.5634. Status indicator or annunciator operates properly.

p.563(b) Unoccupied Control Zone Test. In offices where two or more occupant sensors to

p.563create more than one control zones, simulate an unoccupied condition in the control zone controlled by the occupant sensor. Confirm that at least one other control zone within the office is occupied. Verify and document the following:

p.5631. In 20 minutes or less from the start of the unoccupied condition in the control zone, the occupant sensor uniformly reduces light output of the controlled lighting.

p.5632. Measure the illuminance at the same location as in Step (a). Verify that the light output during unoccupancy is no more than 20 percent of the full light output measured in Step (a)1.

p.5633. The occupant sensing control does not trigger a false on from movement outside of the control zone or from HVAC operation.

p.563(Informational note: The field of view of occupant sensors in the adjacent control zones in offices greater than 250 square feet may overlap, but the field of view should stay away from an adjacent enclosed spaces that is not part of the large office, like conference rooms, and private offices.)

p.5634. Signal sensitivity is adequate to achieve desired control.

p.563(c) Control Zone Size Test. Follow the procedures described in either Method 1 or

p.563Method 2 below.

p.563Method 1: Simulate an unoccupied condition in the control zone controlled by the occupant sensor while standing in an adjacent control zone. Determine the “edge” of

p.563Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes