p.5642025 Nonresidential Appendices the control zone controlled by the occupant sensor by moving toward the occupant sensor until the lights controlled by the occupant sensor turn on as in Step (a) – to simulate an occupied condition for that control zone. Measure, determine and document the following:
p.5641. Measure the distance (in feet) from the “edge” of the control zone to the spot that is directly below the occupant sensor. This is the radius of the control zone.
p.5642. Determine the area of the control zone by using the formula: Area = π*radius2.
p.5643. The area of the control zone must be less than or equal to 600 square feet.
p.564Method 2: Simulate an unoccupied condition for the entire office space. Verify and document the following:
p.5641. Walk thru the space and count the number of zones of lighting turned on automatically as walking thru the space.
p.5642. Document the number of zones being turned on. Determine the size of the office in square footage from construction plans or from other information source.
p.5643. Divide the size of the office by the number of zones. This calculated value is the assessed control zone size (in square feet).
p.5644. If the value is less than or equal to 600 square feet, it passes the test. Otherwise, it fails the test.
p.564(d) Unoccupied Office Test. Simulate an unoccupied condition in all control zones
p.564controlled by all occupant sensors in the office. Verify and document the following:
p.564In 20 minutes or less from the start of the unoccupied condition of the entire office, all general lighting in the office shall turn off.
p.564NA7.6.2.5 Automatic Time Switch Lighting Controls Construction Inspection
p.564Prior to Functional testing, verify and document the following:
p.564(a) The automatic time switch controls are shown on plan documents and are
p.564installed.
p.564(b) Automatic time switch control is programmed with acceptable weekday, weekend,
p.564and holiday (if applicable) schedules.
p.564(c) Document for the automatic time switch programming including weekday,
p.564weekend, holiday schedules as well as all set-up and preference program settings.
p.564(d) The correct time and date are properly set in the time switch.
p.564(e) The battery back-up (if applicable) is installed and energized.
p.564(f) Manual override time limit is set to no more than 2 hours.
p.564(g) Manual override switches located remotely from area with controlled luminaires
p.564allow the user to see the controlled luminaires or have a visual signal or display showing the current state of the controlled luminaires.
p.564Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes