NA7.6.2.6 Automatic Time Switch Lighting Controls Functional Testing

p.5652025 Nonresidential Appendices NA7.6.2.6 Automatic Time Switch Lighting Controls Functional Testing

p.565(a) Occupied Test. Simulate an occupied condition in the controlled space. Verify and

p.565document the following:

p.5651. The automatic time switch control turns the controlled lighting.

p.5652. Reserved

p.565(b) Unoccupied Test. Simulate an unoccupied condition in the controlled space. Verify

p.565and document the following:

p.5651. The automatic time switch control turns off all controlled lighting.

p.5652. During test, for the area controlled by an automatic time-switch control with a configured automatic holiday shut-OFF, the controlled lighting can be turned off automatically by the holiday shut-OFF. For areas that are not required to comply, the lighting is not required to be configured with automatic holiday shut-OFF.

p.5653. For the area controlled by an automatic time-switch control with a time-override located in and for the area, verify the lighting can be turned on manually by initiating the time-override and the lighting is configured to remain ON for no more than 2 hours. For areas that are not required to comply, the lighting can be configured to remain ON for more than 2 hours and until the next scheduled shut off occurs.

p.565NA7.6.3 Demand Responsive Controls Acceptance Tests

p.565NA7.6.3.1 Construction Inspection

p.565Prior to Functional testing, verify and document the following:

p.565(a) The demand responsive control is setup to communicate in one of the following

p.565communication protocols: Wi-Fi, ZigBee, BACnet, Ethernet or other wired or wireless bi-directional communication pathway according to the requirements in Standards § 110.12. The demand responsive control is setup to communicate for the functional testing of NA7.6.3.2.

p.565NA7.6.3.2 Functional Testing

p.565There are three methods to verify the reduction in lighting power due to the demand responsive lighting controls. For methods 1 and 2, buildings with up to seven (7) enclosed spaces requiring demand responsive lighting controls, all spaces shall be tested. For buildings with more than seven (7) enclosed spaces requiring demand responsive lighting controls, sampling may be done on additional spaces with similar lighting systems; sampling shall include a minimum of 1 enclosed space for each group of up to 7 additional enclosed spaces. If the first enclosed space with a demand responsive lighting control in the sample group passes the acceptance test, the remaining building spaces in the sample group also pass. If the first enclosed space with a demand responsive lighting control in the sample group fails the acceptance test, the rest of the enclosed spaces in that group must be tested. If any tested demand responsive lighting control system fails it shall be repaired, replaced, or adjusted until it passes the test. Method 3 tests the entire

p.565Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes