p.5662025 Nonresidential Appendices facility at once, does not require sampling, but requires the facility lighting to be disaggregated from other end-use loads.
p.566Test the reduction in lighting power due to the demand responsive lighting control using one of the following three methods.
p.566NA7.6.3.2.1 Method 1: Illuminance Measurement.
p.566Measure the reduction in illuminance in enclosed spaces required to meet Section 110.12(c), as follows:
p.566(a) In each space, select one location for illuminance measurement. The preferred
p.566measurement location is not in a skylit or primary sidelit area so that the illuminance meter is not in direct view of window or skylight. If this is not possible, perform the test at a time and location at which daylight illuminance provides less than half of the design illuminance. Mark each location to ensure that the illuminance meter can be accurately located.
p.566(b) Full output test
p.5661. Using the manual switches/dimmers in each space, set the lighting system to full output. Note that for lighting system that has been task tuned, override the controls to allow the lighting system to go to full output. Note also that the lighting in areas with photocontrols or occupant vacancy sensors may be at less than full output, or may be off.
p.5662. Take one illuminance measurement at each location, using an illuminance meter.
p.5663. Simulate a demand response condition using the demand responsive control.
p.5664. Take one illuminance measurement at each location with the electric lighting system in the demand response condition.
p.5665. Calculate the area-weighted average reduction in illuminance in the demand response condition, compared with the full output condition. The area-weighted reduction must be at least 15%.
p.566(c) Minimum output test
p.5661. Determine illuminance at minimum output condition:
p.566i. Using the manual switches/dimmers in each space, set the lighting system to minimum output (but not off). Note that the lighting in areas with photocontrols or occupant vacancy sensors may be at more than minimum output, or may be off.
p.566ii. Take one illuminance measurement at each location, using an illuminance meter.
p.5662. Determine illuminance at demand response condition:
p.566i. Simulate a demand response condition using the demand responsive control.
p.566ii. Take one illuminance measurement at each location with the electric lighting system in the demand response condition.
p.566Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes