NA7.6.3.2.2 Method 2: Current measurement.

p.5672025 Nonresidential Appendices 3. Determine compliance:

p.567i. In each space, the illuminance in the demand response condition must not be less than the illuminance in the minimum output condition (but not turned off).

p.567NA7.6.3.2.2 Method 2: Current measurement.

p.567Measure the reduction in electrical current in spaces required to meet Section 110.12, as follows:

p.567(a) At the lighting circuit panel, select at least one lighting circuit that serves

p.567spaces required to meet Section 110.12.

p.567(b) Full output test

p.5671. Using the manual switches/dimmers in each space, set the lighting system to full output. Note that the lighting in areas with photocontrols or occupant vacancy sensors may be at less than full output, or may be off.

p.5672. Take one electric current measurement for each selected circuit.

p.5673. Simulate a demand response condition using the demand responsive control.

p.5674. Take one illuminance measurement at each location with the electric lighting system in the demand response condition.

p.5675. Add together all the circuit currents and calculate the reduction in current in the demand response condition, compared with the full output condition. The combined reduction must be at least 15%.

p.567(c) Minimum output test

p.5671. Using the manual switches/dimmers in each space, set the lighting system to minimum output (but not off). Note that the lighting in areas with photocontrols or occupant vacancy sensors may be at more than minimum output, or may be off.

p.5672. Take one electric current measurement for each selected circuit.

p.5673. Simulate a demand response condition using the demand responsive control.

p.5674. Take one electric current measurement for each selected circuit with the electric lighting system in the demand response condition.

p.5675. In each space, the electric current in the demand response condition must not be less than the electric current in the minimum output condition.

p.567Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes