p.5682025 Nonresidential Appendices NA7.6.3.2.3 Method 3: Full facility current measurement.
p.568Measure the reduction in electrical current of the full facility on the lighting end-use disaggregated circuit for spaces that are required to meet Section 110.12, as follows:
p.568(a) At the circuit panel, select the circuit that serves the lighting load of the entire
p.568facility.
p.568(b) Full output test
p.5681. Using the facility lighting controls, set the lighting system to full output. Note that the lighting in areas with photocontrols or occupant /vacancy sensors may be at less than full output or may be off.
p.5682. Take one electric current measurement on the circuit. This is your pre-event current.
p.5683. Simulate a demand response condition using the demand responsive control.
p.5684. Take one electric current measurement on the circuit. This is your post-event current.
p.5685. Calculate the difference between the pre-event current and the post-event current to determine your wattage reduction.
p.5686. Divide the wattage reduction by the total design wattage of lighting required to meet Section 110.12. The percent reduction in wattage must be at least 15%.
p.568(c) Minimum output test
p.5681. Using the facility controls, set the lighting system to minimum output (but not off). Note that the lighting in areas with photocontrols or occupant /vacancy sensors may be at more than minimum output or may be off.
p.5682. Take one electric current measurement on the circuit. This is your pre-event current.
p.5683. Simulate a demand response condition using the demand responsive control.
p.5684. Take one electric current measurement on the circuit. This is you post event current.
p.5685. The post-event current must not be less than the pre-event current in the minimum output condition.
p.568NA7.6.4 Institutional Tuning Power Adjustment Factor (PAF) Acceptance Tests
p.568For buildings with up to seven (7) enclosed areas claiming the institutional tuning PAF (power adjustment factor), all areas shall be tested. For buildings with more than seven (7) areas claiming this PAF, random sampling may be done on seven of the larger enclosed areas with tuned dimming systems. If any of the areas in the sample group of seven areas fails the acceptance test, another group of seven areas must be tested. If any tested system fails, it shall be tuned until it passes the test.
p.568Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes