NA7.5.4.2 Functional Testing

p.5382025 Nonresidential Appendices (h) Economizer reliability features are present as specified by Standards Section

p.538140.4(e)2D.

p.5381. Indicate N/A for heat recovery bypass.

p.538(i) Economizer inlet damper is designed to modulate up to 100 percent open, and

p.538return air damper to 100 percent closed, without over-pressurizing the building.

p.5381. Indicate N/A for heat recovery bypass.

p.538(j) For systems with DDC controls lockout sensor(s) are either factory calibrated or

p.538field calibrated.

p.538(k) For systems with non-DDC controls, manufacturer’s startup and testing procedures

p.538have been applied.

p.538(l) The economizer has been certified to the Energy Commission as specified by

p.538Section 140.4(e)2Diii.

p.5381. Indicate N/A for heat recovery bypass.

p.538NA7.5.4.2 Functional Testing

p.538Step 1: Disable demand control ventilation systems (if applicable).

p.538Step 2: Enable the economizer and simulate a cooling demand large enough to drive the

p.538system into full economizer cooling mode (e.g., the economizer or heat recovery bypass) is fully open. Verify and document the following:

p.538(a) Economizer or heat recovery bypass damper is 100 percent open and return air

p.538damper is 100 percent closed.

p.5381. If bypass is achieved through heat/energy recovery wheel rotation speed modulation, wheel speed is fully stopped.

p.538(b) All applicable fans and dampers operate as intended to maintain building pressure.

p.538(c) The unit heating is disabled (if unit has heating capability).

p.538Step 3: Disable the economizer and simulate a cooling demand. Verify and document the

p.538following:

p.538(d) Economizer damper closes to its minimum position.

p.538(e) All applicable fans and dampers operate as intended to maintain building pressure.

p.538(f) The unit heating is disabled (if unit has heating capability).

p.538(g) Indicate N/A for this step for heat recovery bypass.

p.538Step 4: If unit has heating capability, simulate a heating demand and set the economizer

p.538so that it is capable of operating (i.e., actual outdoor air conditions are below lockout setpoint). Verify the following:

p.538For economizer systems

p.538(h) The economizer is at minimum position.

p.538(i) Return air damper opens.

p.538Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes