NA7.5.3.2.3.2.4 Visual Inspection of Accessible Duct Sealing

p.5372025 Nonresidential Appendices (b) Visually inspect all accessible portions of the duct system during smoke injection.

p.537(c) The system shall pass the test if one of the following conditions is met:

p.5371. No visible smoke exits the accessible portions of the duct system.

p.5372. Smoke only emanates from the furnace cabinet which is gasketed and sealed by the manufacturer and no visible smoke exits from the accessible portions of the duct system.

p.537NA7.5.3.2.3.2.4 Visual Inspection of Accessible Duct Sealing

p.537For altered existing duct systems that are unable to pass the leakage test in Section NA7.5.3.2.3.2.1 and a smoke test per Section NA7.5.3.2.3.2.3 shall be verified that all accessible leaks have been sealed. Visually inspect to verify that the following locations have been sealed:

p.537(a) Connections to plenums and other connections to the air-handling unit.

p.537(b) Refrigerant line and other penetrations into the air-handling unit.

p.537(c) Air handler access door or panel (do not use permanent sealing material, metal

p.537tape is acceptable).

p.537(d) Register boots sealed to surrounding material.

p.537(e) Connections between lengths of duct, as well as connections to takeoffs, wyes,

p.537tees, and splitter boxes.

p.537NA7.5.4 Air Economizer Controls and Exhaust Air Heat Recovery

p.537NA7.5.4.1 Construction Inspection

p.537Prior to Functional Testing, verify and document the following:

p.537(a) Economizer or heat recovery bypass high limit shutoff control complies with Table

p.537140.4-G of Standards §140.4(e)2.

p.537(b) If the high-limit control is fixed dry-bulb or fixed enthalpy + fixed dry-bulb, it shall

p.537have an adjustable setpoint.

p.537(c) Economizer or heat recovery bypass lockout control sensor is located to prevent

p.537false readings.

p.537(d) Sensor performance curve is provided by factory with economizer or heat recovery

p.537bypass instruction material.

p.537(e) Sensor output value measured during sensor calibration is plotted on the

p.537performance curve.

p.537(f) Economizer or heat recovery bypass damper moves freely without binding.

p.5371. Indicate if bypass control is achieved through heat/energy recovery wheel rotation speed modulation as means other than air dampers

p.537(g) Economizer or heat recovery bypass has control systems, including two-stage or

p.537electronic thermostats, that cycle compressors off when economizers or heat recovery bypass can provide partial cooling.

p.537Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes