p.5362025 Nonresidential Appendices (b) For newly installed or altered ducts, verify that cloth backed rubber adhesive duct
p.536tape has not been used.
p.536(c) Temporarily seal all the supply registers and return grilles, except for one large
p.536centrally located return grille or the air handler cabinet access door or panel. Verify that all outside air dampers and/or economizers are sealed prior to pressurizing the system.
p.536(d) Attach the fan flowmeter device to the duct system at the unsealed return grille or
p.536the air handler cabinet access door or panel.
p.536(e) Install a static pressure probe at a supply register located close to the air handler,
p.536or at the supply plenum.
p.536(f) Adjust the fan flowmeter to produce a positive 25 Pa (0.1 inches water) pressure at
p.536the supply register or the supply plenum with respect to the outside or with respect to the building space with the entry door open to the outside.
p.536(g) Record the flow through the flowmeter, this is the duct leakage flow at 25 Pa (0.1
p.536inches water).
p.536(h) Divide the duct leakage flow by the nominal air handler airflow determined by the
p.536procedure in Section NA7.5.3.2.3.1 and convert to a percentage. If the duct leakage flow percentage is equal to or less than the target compliance criterion from Table NA7.5.3-1, the system passes.
p.536NA7.5.3.2.3.2.2 Sealing of All Accessible Leaks
p.536For altered existing duct systems that are unable to pass the leakage test in Section NA7.5.3.2.3.2.1, the objective of this test is to verify that all accessible leaks are sealed. The following procedure shall be used:
p.536(a) Complete the leakage test specified in Section NA7.5.3.2.3.2.1.
p.536(b) Seal all accessible ducts.
p.536(c) After sealing is complete, again use the procedure in NA7.5.3.2.3.2.1 to measure the
p.536leakage after duct sealing.
p.536(d) Complete the Smoke Test as specified in NA7.5.3.2.3.2.3.
p.536(e) Complete the Visual Inspection as specified in NA7.5.3.2.3.2.4.
p.536All duct systems that fail to pass the leakage test specified in Section NA7.5.3.2.3.2.1 shall be tested and inspected by an ATT to verify that all accessible ducts have been sealed and damaged ducts have been replaced.
p.536NA7.5.3.2.3.2.3 Smoke-Test of Accessible-Duct Sealing
p.536For altered existing ducts that fail the leakage tests, the objective of the smoke test is to confirm that all accessible leaks have been sealed. The following procedure shall be used:
p.536(a) Inject either theatrical or other non-toxic smoke into a fan pressurization device that is
p.536maintaining a duct pressure difference of 25 Pa (0.1 inches water) relative to the duct surroundings, with all grilles and registers in the duct system sealed.
p.536Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes