p.5392025 Nonresidential Appendices For HRV/ERV or DOAS systems:
p.539(j) Heat recovery bypass control modulates bypass damper/wheel speed to control
p.539temperature setpoint.
p.539Step 5: Turn off the unit. Verify and document the following:
p.539(k) Economizer damper closes completely.
p.539(l) Indicate N/A for this step for heat recovery bypass.
p.539Step 6: Restore demand control ventilation systems (if applicable) and remove all system
p.539overrides initiated during the test.
p.539NA7.5.5 Demand Control Ventilation (DCV) Systems
p.539NA7.5.5.1 Construction Inspection
p.539Prior to Functional Testing, verify and document the following:
p.539(a) Carbon dioxide control sensor is factory calibrated as specified by §120.1(d)4F.
p.539(b) The sensor is located in the high density space between 3 ft and 6 ft above the
p.539floor or at the anticipated level of the occupants’ heads.
p.539(c) DCV control setpoint is at or below the CO2 concentration permitted by
p.539§120.1(d)4C.
p.539NA7.5.5.2 Functional Testing
p.539Step 1: Disable economizer controls.
p.539Step 2: Simulate a signal at or slightly above the CO2 concentration setpoint required by
p.539§120.1(d)4C. Verify and document the following:
p.539(a) For single zone units, outdoor air damper modulates open to satisfy the total
p.539ventilation air called for in the Certificate of Compliance.
p.539(b) For multiple zone units, the zone damper (or outdoor air damper when applicable)
p.539modulates open to satisfy the zone ventilation requirements.
p.539Step 3: Simulate signal well below the CO2 setpoint. Verify and document the following:
p.539(c) For single zone units, outdoor air damper modulates to the design minimum value.
p.539(d) For multiple zone units, the zone damper (or outdoor air damper when applicable)
p.539modulates to satisfy the reduced zone ventilation requirements.
p.539Step 4: Restore economizer controls and remove all system overrides initiated during the
p.539test.
p.539Step 5: With all controls restored, apply CO2 calibration gas at a concentration slightly
p.539above the setpoint to the sensor. Verify that the outdoor air damper modulates open to satisfy the total ventilation air called for in the Certificate of Compliance.
p.539Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes