RA3.5.3.4.2 Homes with Conditioned Space Over Garage

p.3902025 Residential Appendices RA3.5.3.4.2 Homes with Conditioned Space Over Garage

p.390The separation between conditioned space (house) and the garage shall be insulated to create a continuous thermal barrier. All rim and band joists adjoining conditioned space shall be airtight and insulated.

Figure RA3.5-1 Homes with Conditioned Space Over Garage – Batt and Blanket Insulation
Figure RA3.5-1 Homes with Conditioned Space Over Garage – Batt and Blanket Insulation — p.390

p.390Figure RA3.5-1 Homes with Conditioned Space Over Garage – Batt and Blanket Insulation

p.390RA3.5.3.4.3 Homes with No Conditioned Space Over Garage

p.390The band joist where the garage transitions to an attic above conditioned space shall have an air barrier installed in contact with the edge of the attic insulation.

Figure RA3.5-2 Homes with No Conditioned Space Over Garage – Batt and Blanket Insulation
Figure RA3.5-2 Homes with No Conditioned Space Over Garage – Batt and Blanket Insulation — p.390

p.390Figure RA3.5-2 Homes with No Conditioned Space Over Garage – Batt and Blanket Insulation

p.390RA3.5.4 LOOSE FILL INSULATION

p.390These procedures detail the installation and inspection protocols necessary to qualify for Quality Insulation Installation (QII) of loose-fill insulation. These procedures must be field verified before the building construction permit is finalized.

p.390These procedures are to be followed by the insulation installer and an ECC-rater must verify conformance to meet the requirements of Sections 150.1(c)1E or 170.2(a)6, and 110.7 of the Standards.

p.390– Residential Field Verification and Diagnostic Test Protocols