p.3912025 Residential Appendices RA3.5.4.1 Thermal Specification
p.391This insulation type is manufactured to be blown or sprayed into framed cavity walls, floors, and ceilings. It is installed with or without a net depending on the loose-fill type or in special installations where netting is required, such as below a roof deck or under floors. Its overall R- value is dependent on the installed density and installed thickness. Specific product R-values are readily available from the manufacturer for the specific materials being installed. R-value and coverage chart of the product is typically marked on the bag which the insulation was drawn from and from the manufacturer's product data sheet or product specification information. The installed insulation must meet the R-value stated on the compliance documentation.
p.391RA3.5.4.1.1 Requirements for Walls, Roof/Ceilings and Floors
p.391(a) Materials shall comply with, and be installed in conformance with, all applicable building
p.391codes for building. California Building Code (including, but not limited to, California Electric Code Section 719) and installed to meet all applicable fire codes.
p.391(b) Materials shall meet California Quality Standards for Insulating Material, Title 24, Part 12,
p.391Chapter 4, Article 3, listed in the California Department of Consumer Affairs Consumer Guide and Directory of Certified Insulating Materials.
p.391(c) Materials shall comply with flame spread rating and smoke density requirements of Chapter
p.39126 and Section 706 of the Title 24, Part 2: all installations with exposed facings must use fire retardant facings which have been tested and certified not to exceed a flame spread index (FSI) of 25 and a smoke development index (SDI) of 450. Insulation facings that do not touch a ceiling, wall, or floor surface, and faced batts on the undersides of roofs with an air space between the ceiling and facing are considered exposed applications.
p.391(d) Materials shall be installed according to manufacturer specifications and instructions.
p.391(e) Hard covers or draft stops shall be placed over all drop ceiling areas and interior wall cavities
p.391to keep insulation in place and stop air movement. If hard covers or draft stops are missing or incomplete, they shall be completed before insulation is installed.
p.391(f) Required eave ventilation shall not be obstructed - the net free-ventilation area of the eave
p.391vent shall be maintained.
p.391(g) Eave vent baffles shall be installed to prevent air movement under or into the batt.
p.391(h) Insulation shall cover all recessed lighting fixtures. If the fixtures are not rated for insulation
p.391contact (IC) and air tight, the fixtures shall be replaced.
p.391(i) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance
p.391insulation contact (IC), have a label that certifies it as airtight with leakage less than 2.0 cfm @ 75 Pa when tested to ASTM E283, and shall be sealed with a gasket or caulk between the light's housing and the ceiling.
p.391(j) Loose-fill insulation shall be must completely fill the framed cavity.
p.391(k) Loose-fill insulation shall be installed so that they will be in contact with the air barrier.
p.391Appendix RA3– Residential Field Verification and Diagnostic Test Protocols