RA3.5.4.1.2 R-value Measurement Equipment

p.3922025 Residential Appendices RA3.5.4.1.2 R-value Measurement Equipment

p.392The ECC-rater shall measure the installed thickness and density of insulation in at least 6 random locations on walls, roof/ceilings, and floors (i.e., 6 measurements per opaque surface type: wall, roof/ceiling, or floor) to ensure minimum thickness levels and the installed density meets the R- value specified on the Certificate of Compliance, and all other required compliance documentation. For walls, measurement areas shall include low and high areas of the insulated assembly and the ECC-rater shall verify density measurements are consistent with the manufacturer's coverage chart.

p.392RA3.5.4.1.3 Certificates

p.392(a) All provisions of Residential Appendix RA2 shall be met. All Insulation Certificates of

p.392Installation signed by the insulation installer shall be provided stating the installation is consistent with the Certificate of Compliance, plans and specifications for which the building permit was issued. The insulation installer shall complete all applicable sections of the Certificate of Installation form and attach a bag label or a manufacturer's coverage chart for every different type of loose-fill insulation material used.

p.392(b) For loose-fill insulation, compliance information shall include the minimum installed weight­

p.392per-square-foot (or the minimum weight per cubic foot) consistent with the manufacturer's labeled installed-design-density for the desired R-value, and the number of inches required to achieve the desired R-value.

p.392RA3.5.4.1.4 Certificates and Availability

p.392All provisions of Residential Appendix RA2 shall be met. The Insulation Certificate of Installation, with insulation material bag labels or coverage charts attached, signed by the insulation installer, shall be available on the building site for each of the ECC-rater's verification inspections.

p.392RA3.5.4.2 Wall Insulation

p.392(a) Wall stud cavities shall be caulked, foamed, or otherwise sealed to provide a substantially air­

p.392tight envelope to the outdoors, attic, garage and crawl space. Special attention shall be paid to plumbing and wiring penetrations through the top plates, electrical boxes that penetrate the sheathing, and the sheathing seal to the bottom plate. All gaps in the air barrier shall be caulked or sealed with expansive, or minimally expansive, foam.

p.392(b) Bottom plates of framed and non-framed assemblies shall be sealed to the ground subfloor or

p.392slab, and above ground subfloor.

p.392(c) Insulation shall uniformly fill the cavity side-to-side, top-to-bottom, and front-to-back.

p.392(d) Loose fill insulation shall be installed to fill the cavity and be in contact with the sheathing on

p.392the back and the wallboard on the front - no gaps or voids.

p.392(e) Loose fill wall insulation shall be installed to fit around wiring, plumbing, and other

p.392obstructions.

p.392– Residential Field Verification and Diagnostic Test Protocols