p.3932025 Residential Appendices (f) Non-standard-width cavities shall be filled with insulation fitted into the space without
p.393excessive compression.
p.393(g) The installer shall certify on the Certificate of Installation forms that the manufacturer's
p.393minimum weight-per-square-foot requirement has been met.
p.393RA3.5.4.2.1 Narrow-Framed Cavities
p.393(a) Non-standard width cavities shall be filled with insulation to snuggly fit into the space, or with
p.393minimally expansive foam sealing material.
p.393(b) Narrow spaces less than 1 inch in width at windows and door jambs, shall be filled with
p.393minimally expansive foam sealing. In cases where the manufacturer's warranty would be void if minimally expanding foam is used to seal the gap between the window frame or door jamb, the cavity must be airtight and filled with insulation snuggly fitted (with limited compression) in the space.
p.393(c) Narrow spaces less than 2 inches in width, such as between studs at building corners, and at
p.393the intersection of interior partition walls to exterior walls, shall be filled with insulation snuggly fitted in the space, or with minimally expansive foam sealing.
p.393RA3.5.4.2.2 Special Situations--Installation Prior to Exterior Sheathing or Lath
p.393(a) Hard to access wall stud cavities, such as corner channels, wall intersections, and behind
p.393tub/shower enclosures shall be insulated to the proper R-value. In most cases this can only be completed prior to the installation of the tub/shower enclosure, the exterior sheathing, or the exterior stucco lath.
p.393(b) An air barrier shall be installed on the inside of the exterior wall(s) directly adjacent to the
p.393tub/shower enclosure.
p.393RA3.5.4.2.3 Special Situations--Obstructions
p.393(a) Insulation shall completely fill around wiring and plumbing without compression.
p.393(b) Insulation shall fill between the sheathing and the rear of electrical boxes and phone boxes.
p.393(c) In cold climates, where water pipes may freeze (such as Climate Zones 2, 11-14 and 16) pipes
p.393shall have at least 1/2 of the insulation between the water pipe and towards the outside surface of the exterior wall. As much insulation as possible shall be placed between the pipe and the outside (without compression), and remaining insulation shall be placed between the pipe and the interior assembly material.
p.393RA3.5.4.2.4 Special Situations--Rim Joists
p.393(a) All rim-joists shall be insulated to the same R-value as the adjacent walls.
p.393(b) The insulation shall be installed without gaps, voids, or excessive compression.