p.4542025 Residential Appendices a, b = Qualification distance coefficients (unitless), see Table 4.4.6-2, CFA = Conditioned floor area of the dwelling unit (ft2), and n = Number of water heaters in the dwelling unit (unitless).
| Building Type | Coefficient a Non-Recirculating | Coefficient a Recirculating | Coefficient b Non-Recirculating | Coefficient b Recirculating |
|---|---|---|---|---|
| Single Family One story | 10 | 22.7 | 0.0095 | 0.0099 |
| Single Family Two story | 15 | 11.5 | 0.0045 | 0.0095 |
| Single Family Three story | 10 | 0.5 | 0.0030 | 0.014 |
| Multifamily One story | 7.5 | n/a | 0.0080 | n/a |
| Multifamily Two or more story | 7.5 | n/a | 0.0050 | n/a |
p.454RA4.4.7 Recirculation Systems
p.454RA4.4.7.1 Installation requirements for all recirculation systems
p.454The supply portion of each circulation loop, the first five feet of branches off the loop and the dedicated return line are insulated based on the conductivity range in TABLE 120.3-A and the insulation level shall be selected from the fluid temperature range based on the thickness requirements in TABLE 120.3-A and the insulation shall be installed in accordance with Proper Installation of Pipe Insulation. Other hot water piping shall meet the requirements of §150.0(j) and be installed in accordance with Proper Installation of Pipe Insulation R4.4.1.
p.454A check valve shall be installed in the recirculation loop to prevent unintentional circulation of the water (thermo-siphoning) and back flow when the system is not operating. This check valve may be included with the pump.
p.454The hot water distribution system piping from the water heater(s) to the fixtures and appliances must take the most direct path. For example, in a house with more than 1-story and the water heater in the garage, this requirement would exclude running hot water supply piping from the water heater to the attic, and then running the line back down to a first floor point of use.
p.454The recirculation pump can be located external to the water heater or be integral to the water heater.
p.454The manufacturer(s) of the recirculation pump and the controls shall provide installation and operation instructions that provide details of the operation of the pump and controls, and such instructions shall be available at the jobsite for inspection.