p.4532025 Residential Appendices Weighted_Distance = x * d_MasterBath + y * d_Kitchen + z * d_FurthestThird
| RA4.4.5 Point of Use (POU) This measure requires that stand-alone tub must use requirement most houses | all hot water fixtures no more pipe per run will require multiple Table | in the dwelling unit, than defined in Table water heaters. 4.4.5 | with the exception of a 4.4.5. To meet this |
| Size Nominal (Inch) | Length of Pipe (feet) | ||
| 3/8” | 15 | ||
| 1/2” | 10 | ||
| 3/4” | 5 |
p.453x, y, and z = Weighted Distance coefficients (unitless), see Table 4.4.6-1.
p.453d_MasterBath = The plan view, straight line distance from the water heater to the furthest fixture served by that water heater in the master bathroom (feet).
p.453d_Kitchen = The plan view, straight line distance from the water heater to the furthest fixture served by that water heater in the kitchen (feet).
p.453d_FurthestThird = The plan view, straight line distance from the water heater to the furthest fixture served by that water heater in the furthest room7 in the dwelling unit
| Distribution System | x | y | z |
|---|---|---|---|
| Non-Recirculating | 0.4 | 0.4 | 0.2 |
| Recirculating | 0.0 | 0.0 | 1.0 |
p.452(a) Measurements shall be made to the nearest half foot.
p.452(b) If a combination of piping is used in a single run, then one half the allowed length of each
p.452size is the maximum installed length.
p.453Note that the calculations are only based on horizontal plan view distance measurements from the center of the water heater to the center of the use point in the designated location8. Vertical pipe run lengths (for example, the vertical distance from the first to second floor) is neglected in the calculations. Use points that are located on floors different than the water heater would have their location translated to the floor where the water heater is located.
p.452(c) The hot water distribution system piping from the water heater(s) to the fixtures and
p.452appliances must take the most direct path. For example, in a house with more than 1 story and the water heater in the garage, this requirement would exclude running hot water supply piping from the manifold to the attic, and then running the line back down to a first floor point of use.
p.453In single family homes with multiple water heaters, the Weighted Distance “z term” calculation is performed for each water heater to arrive at a Furthest Third term averaged over each of the “n” water heaters installed. For a non-recirculating distribution system, the resulting Weighted Distance calculation would include the Master Bath, the Kitchen and an average of the Furthest Third term for each of the installed water heaters. (For recirculating systems, similarly the Furthest Third term would represent an average across the “n” water heaters.)
p.452(d) Hot water piping shall be insulated to a level that meets the requirements of §150.0(j) and
p.452be installed in accordance with Proper Installation of Pipe Insulation R4.4.1.
p.452RA4.4.6 Compact Hot Water Distribution System
p.452To receive the Compact Hot Water Distribution System credit (available for single family homes and multifamily dwellings served by individual water heaters), plan calculations must be completed that demonstrate that the water heater to fixture proximity is more compact than a threshold criteria that is defined based on the dwelling unit conditioned floor area and number of stories. Compactness is characterized by calculating the “Weighted Distance” from the water heater to key fixtures and the threshold criteria is identified by the “Qualification Distance”. (The Qualification Distance is calculated directly by the ACM.) Determination of the Weighted Distance for a particular floor plan is dependent on whether it is a non-recirculating or a recirculating distribution system, with the recirculation option only available for single family homes.
p.453The Qualification Distance is a function of conditioned floor area (CFA), number of stories, and number of installed water heaters. The Qualification Distance for systems with multiple water heaters is identified by using the equation for the appropriate distribution system (recirculation or non-recirculation), and dividing by the number of water heaters installed as shown in the Equation below:
p.453Qualification Distance = (a + b * CFA) / n Where:
p.452Calculation of the Weighted Distance varies depending on the type of system being installed. The calculation is based on a equation with modifications based on the distribution system type. In each case the basis of the calculation is the plan-view, straight line distance from the water heater to the center of the further use point fixture in three locations of the dwelling unit, two of which are the master bathroom and the kitchen. It is calculated using the following equation:
p.4537 Because the Master Bath and Kitchen have unique separate terms, the d_FurthestThird fixture must located in neither of these rooms. The laundry room is excluded, and shall not be used as the furthest third fixture. In multifamily cases where there is not another qualifying use point, the d_FurthestThird term equals zero.
p.4538 For example, a shower/tub combination would take the measurement from the fixture supply outlet of the shower/tub, while a two sink lavatory in the master bath would take the measurement from the fixture supply outlet of the lavatory furthest from the water heater.