p.4512025 Residential Appendices A variable speed circulation pump with pump differential pressure control shall be installed. The circulation pump design flow rate should be calculated to meet the design hot water return temperature based on the calculated distribution system heat losses and the design hot water supply temperature. The circulation pump specified should be the smallest pump required to meet the design flow rate as calculated and documented by the responsible person associated with the project.
p.451Each thermostatic balancing valve shall be installed after the last fixture on the hot water supply riser it serves. As part of the installer’s start-up procedure, the installer shall perform the following:
p.451(a) Close all fixtures in the domestic water system.
p.451(b) Start the circulation pump at a constant speed, targeting the circulation pump design
p.451flow, and allow the system 60 minutes to warm up.
p.451(c) Verify that the temperature at the last riser does not exceed 120°F.
p.451(d) If the temperature at the last riser exceeds 120°F, adjust the pump speed down and
p.451repeat the procedure, allowing 30 minutes for warm up.
p.451(e) Once the temperature at the last riser is equal to or less than 120°F, record the pump
p.451differential pressure and set the pump into differential pressure control mode using the recorded differential pressure as the set point.
p.451RA4.4.4 Central Parallel Piping
p.451This hot water distribution system is comprised of one or more manifolds located relatively close to the water heater and pipes running from the manifold to individual fixtures and appliances. The manifolds may have valves for each pipe running from the manifold to individual fixtures and appliances. These valves must be readily accessible in accordance with the plumbing code. The measured length of pipe from the water heater each central manifold shall not exceed 15 feet (measured to the nearest half foot).
p.451The hot water distribution system piping from the manifold to the fixtures and appliances must take the most direct path. For example, in a house with more than 1-story and the water heater in the garage, this requirement would exclude running hot water supply piping from the manifold to the attic, and then running the line back down to a first floor point of use.
p.451The hot water distribution piping must be separated by at least two inches from any other hot water supply piping, and at least six inches from any cold water supply piping or the hot water supply piping must be insulated based on the conductivity range in TABLE 120.3-A and the insulation level shall be selected from the fluid temperature range based on the thickness requirements in TABLE 120.3-A.
p.451Other hot water piping shall be insulated to a level that meets the requirements of §150.0(j) and be installed in accordance with Proper Installation of Pipe Insulation R4.4.1.
p.451– Eligibility Criteria for Energy Efficiency Measures