RA4.4.8 Recirculation with non-demand controls

p.4552025 Residential Appendices RA4.4.8 Recirculation with non-demand controls

p.455All recirculation controls with the exception of demand recirculation control systems fall under this category.

p.455(a) More than one circulation loop may be installed. Each loop shall have its own pump and

p.455controls.

p.455(b) The active control shall be either: timer, temperature, or time and temperature. Timers

p.455shall be set to less than 24 hours. The temperature sensor shall be connected to the piping and to the controls for the pump.

p.455RA4.4.9 Demand Recirculation; Manual Control

p.455Demand controlled recirculation systems shall operate “on-demand”, meaning that pump operation shall be initiated shortly prior to the hot water draw. The controls shall operate on the principal of shutting off the pump with a sensed rise in pipe temperature (Delta-T). For this measure a manual switch is used to activate the pump.

p.455(a) More than one circulation loop may be installed. Each loop shall have its own pump and

p.455controls.

p.455(b) Manual controls shall be located in the kitchen, bathrooms, and any hot water fixture

p.455location that is at least 20 feet (measured along the hot water piping) from the water heater.

p.455(c) Manual controlled systems may be activated by wired or wireless mechanisms, Manual

p.455controls shall have standby power of 1 watt or less.

p.455(d) Pump and demand control placement meets one of the following criteria.

p.4551. When a dedicated return line has been installed the pump, demand controls and thermo-sensor are installed at the end of the supply portion of the recirculation loop (typically under a sink); or

p.4552. The pump and demand controls are installed on the return line near the water heater and the thermo-sensor is installed in an accessible location as close to the end of the supply portion of the recirculation loop as possible (typically under a sink), or

p.4553. When the cold water line is used as the return, the pump, demand controls and thermo-sensor is installed in an accessible location at the end of supply portion of the hot water distribution line (typically under a sink).

p.455(e) Insulation is not required on the cold water line when it is used as the return.

p.455(f) Demand controls shall be able to shut off the pump in accordance with one of the

p.455following two methods:

p.4551. After the pump has been activated, the controls shall allow the pump to operate until the water temperature at the thermo-sensor rises not more than 10oF (5.6 oC ) above the initial temperature of the water in the pipe, or

p.4552. The controls shall not allow the pump to operate when the temperature in the pipe exceeds 102oF (38.9 oC).

p.455– Eligibility Criteria for Energy Efficiency Measures