p.4582025 Residential Appendices 1. After the pump has been activated, the controls shall allow the pump to operate until the water temperature at the thermo-sensor rises not more than 10oF (5.6 oC ) above the initial temperature of the water in the pipe, or 2. The controls shall not allow the pump to operate when the temperature in the pipe exceeds 102oF (38.9 oC). 3. The controls shall limit pump operation to a maximum of 10 minutes following any activation. This is provided in the event that the normal means of shutting off the pump have failed.
p.458Recirculation systems shall also meet the requirements of §110.3.
p.458RA4.4.14 Verified Pipe Insulation for Single Dwelling
p.458Consistent with the requirements of RA3.6.2, this measure requires an ECC-rater to verify that all hot water piping is insulated correctly.
p.458RA4.4.15 Verified Parallel Piping
p.458Consistent with the requirements of RA4.4.4 this measure requires an ECC-rater to verify that the length of pipe between the water heater and each central manifold does not exceed 5 feet and to verify pipe insulation.
p.458RA4.4.16 Verified Compact Hot Water Distribution System Expanded Credit
p.458A ECC-rater verification is required in order to obtain this credit. To meet the Compact Hot Water Distribution System Expanded Credit eligibility requirements, the requirements in RA4.4.6 must be met. In addition, the following field verifications are required:
p.458(a) No hot water piping >1” diameter piping is allowed,
p.458(b) Length of 1” diameter piping is limited to 8 ft or less,
p.458(c) Two and three story buildings cannot have hot water distribution piping in the attic,
p.458unless the water heater is also located in the attic and,
p.458(d) Eligible recirculating systems must be Verified Demand Recirculation: Manual Control
p.458RA4.4.17 Verified Demand Recirculation: Manual Control
p.458This measure shall include a visual ECC-rater inspection to verify that the demand pump, manual controls and thermo-sensor are present and operating properly.
p.458RA4.4.18 Verified Demand Recirculation: Sensor Control
p.458This measure shall include a visual ECC-rater inspection to verify that the demand pump, sensor controls and thermo-sensor are present and operating properly.
p.458RA4.4.19 Multiple Dwelling Units: Master Mixing Valves
p.458For central systems with hot water piping serving multiple dwelling units master mixing valves (MMV) shall meet the following minimum specification, installation, and startup requirements.