p.4592025 Residential Appendices RA4.4.19.1 Plumbing Plans
p.459The plumbing plans shall include the following MMV specification at a minimum:
p.459(a) Manufacturer’s installation and commissioning instructions and plumbing drawings.
p.459(b) MMV conforms to the American Society of Sanitation Engineers (ASSE) 1017-2009
p.459standard, Performance Requirements for Temperature Actuated Mixing Valves for Hot Water Distribution Systems.
p.459(c) Water mixing parameters and associated values:
p.4591. Input parameters
p.459A. Recirculation pump flow rate
p.459B. Mixing valve outlet water temperature
p.459C. Recirculation return water temperature
p.459D. Mixing valve hot inlet water temperature
p.4592. Calculated parameters
p.459A. Percentage of water flow returning to cold side of MMV
p.459B. Percentage of water flow returning to hot side of MMV
p.4593. Manufacturer’s operating parameter
p.459A. Maximum water mixing ratio
p.459These input parameters shall be used to calculate percentage of water flow on cold side and hot side of MV during recirculation water flow only condition to determine if the water mixing ratio exceeds mixing capability of the specified master mixing valve. If the calculated water flow ratio to the MMV inlet exceeds manufacturer’s recommendations for that valve, the designer shall provide instructions to commission the balancing valve to eliminate temperature creep to mitigate scalding risk after periods of no water draw.
p.459RA4.4.19.2 Installation
p.459Installation of MMV shall meet manufacturer’s instruction and the following requirements at a minimum:
p.459(a) The MMV shall be installed on the central heating plant hot water supply outlet header
p.459leading to the recirculation loop. (b) Check valves installed on the recirculation return line and cold-water line to inlet cold
p.459connection of MMV and on recirculation return piping leading back to storage tank or water heater. (c) Isolation valves installed on the inlet cold water, inlet recirculation return, inlet hot and
p.459outlet connections to MMV and on recirculation return piping connection to storage tank or water heater. (d) Balancing valve installed on the recirculation return piping to the water heater for MMVs
p.459that cannot 100% close the hot inlet port during operation. (e) Thermometers installed on the outlet of the MMV and on the recirculation return line
p.459next the water pump.
p.459– Eligibility Criteria for Energy Efficiency Measures