RA4.4.11 Multiple Dwelling Units: Recirculation Temperature Modulation Control

p.4572025 Residential Appendices RA4.4.11 Multiple Dwelling Units: Recirculation Temperature Modulation Control

p.457A recirculation temperature modulation control shall reduce the hot water supply temperature when hot water demand is determined to be low by the control system. The control system may use a fixed control schedule or dynamic control schedules based measurements of hot water demand. The daily hot water supply temperature reduction, which is defined as the sum of temperature reduction by the control in each hour within a 24-hour period, shall be more than 50 degrees Fahrenheit to qualify for the energy savings credit.

p.457Recirculation systems shall also meet the requirements of §110.3.

p.457RA4.4.12 Multiple Dwelling Units: Recirculation Continuous Monitoring Systems

p.457Systems that qualify as a recirculation continuous monitoring systems for domestic hot water systems serving multiple dwelling units shall record no less frequently than hourly measurements of key system operation parameters, including hot water supply temperatures, hot water return temperatures, and status of gas valve relays of water heating equipment. The continuous monitoring system shall automatically alert building operators of abnormalities identified from monitoring results.

p.457Recirculation systems shall also meet the requirements of §110.3.

p.457RA4.4.13 Multiple Dwelling Units: Demand Recirculation

p.457Demand controlled recirculation systems shall operate “on-demand”, meaning that pump operation shall be initiated shortly prior to, or by a hot water draw. The controls shall operate on the principal of shutting off the pump with a sensed rise in pipe temperature (Delta-T). For this measure sensor or manual controls may be used to activate the pump(s).

p.457(a) Manual or sensor controls shall be installed and if powered, have standby power of 1 watt

p.457or less. Controls may be located in individual units or on the loop. Controls may be activated by wired or wireless mechanisms, including buttons, motion sensors, door switches and flow switches.

p.457(b) Pump and control placement shall meet one of the following criteria:

p.4571. When a dedicated return line has been installed the pump, controls and thermo-sensor are installed at the end of the supply portion of the recirculation loop; or

p.4572. The pump and controls are installed on the dedicated return line near the water heater and the thermo-sensor is installed in an accessible location as close to the end of the supply portion of the recirculation loop as possible, or

p.4573. When the cold water line is used as the return, the pump, demand controls and thermosensor shall be installed in an accessible location at the end of supply portion of the hot water distribution line (typically under a sink).

p.457(c) Insulation is not required on the cold water line when it is used as the return.

p.457(d) Demand controls shall be able to shut off the pump in accordance with these three

p.457methods:

p.457– Eligibility Criteria for Energy Efficiency Measures