NA7.5.8.1 Construction Inspection

p.5412025 Nonresidential Appendices (b) Verify that this is within 5 percent of the submittal data for the pump.

p.541Step 2: Reopen the pump discharge isolation valves. Automatically close all valves on the

p.541systems being tested. If 3-way valves are present, close off the bypass line. Verify and document the following:

p.541(c) The valves automatically close.

p.541(d) Record the pressure differential across the pump.

p.541(e) Verify that the pressure differential is within 5 percent of the reading from Step 1

p.541for the pump that is operating during the valve test.

p.541Step 3: Restore system to correct operating conditions.

p.541NA7.5.8 Supply Water Temperature Reset Controls

p.541NA7.5.8.1 Construction Inspection

p.541Prior to Functional Testing, verify and document the following:

p.541(a) Supply water temperature sensors have been either factory or field calibrated.

p.541NA7.5.8.2 Functional Testing

p.541Step 1: Change reset control variable to its maximum value. Verify and document the

p.541following:

p.541(a) Chilled or hot water temperature setpoint is reset to appropriate value.

p.541(b) Verify that actual supply temperature changes to within 2 percent of the new

p.541setpoint.

p.541Step 2: Change reset control variable to its minimum value. Verify and document the

p.541following:

p.541(c) Chilled or hot water temperature setpoint is reset to appropriate value.

p.541(d) Verify that actual supply temperature changes to within 2 percent of the new

p.541setpoint.

p.541Step 3: Restore reset control variable to automatic control. Verify and document the

p.541following:

p.541(e) Chilled or hot water temperature set-point is reset to appropriate value.

p.541(f) Verify that actual supply temperature changes to within 2 percent of the new

p.541setpoint.

p.541NA7.5.9 Hydronic System Variable Flow Controls

p.541NA7.5.9.1 Construction Inspection

p.541Prior to Functional Testing, verify and document the following:

p.541(a) The static pressure location, setpoint, and reset control meets the requirements of

p.541the Standards Section 140.4(k)6B.

p.541Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes