NA7.5.3 Air Distribution Systems

p.5322025 Nonresidential Appendices (g) Outside air damper is at minimum position.

p.532Step 4: Simulate cooling demand during occupied condition. Lock out economizer (if

p.532applicable). Verify and document the following:

p.532(h) Supply fan operates continually.

p.532(i) The unit provides cooling.

p.532(j) No heating is provided by the unit.

p.532(k) Outside air damper is at minimum position.

p.532Step 5: Simulate operation in the dead band during unoccupied mode. Verify and

p.532document the following:

p.532(l) Supply fan is off.

p.532(m)Outside air damper is fully closed.

p.532(n) Neither heating nor cooling is provided by the unit.

p.532Step 6: Simulate heating demand during unoccupied conditions. Verify and document the

p.532following:

p.532(o) Supply fan is on (either continuously or cycling).

p.532(p) Heating is provided by the unit.

p.532(q) No cooling is provided by the unit.

p.532(r) Outside air damper is either closed or at minimum position.

p.532Step 7: Simulate cooling demand during unoccupied condition. Lock out economizer (if

p.532applicable). Verify and document the following:

p.532(s) Supply fan is on (either continuously or cycling).

p.532(t) Cooling is provided by the unit.

p.532(u) No heating is provided by the unit.

p.532(v) Outside air damper is either closed or at minimum position.

p.532Step 8: Simulate manual override during unoccupied condition. Verify and document the

p.532following:

p.532(w)System operates in “occupied” mode.

p.532(x) System reverts to “unoccupied” mode when manual override time period expires.

p.532Step 9: Restore economizer and demand control ventilation systems (if applicable) and

p.532remove all system overrides initiated during the test.

p.532NA7.5.3 Air Distribution Systems

p.532Purpose and Scope

p.532(a) NA7.5.3 contains procedures for acceptance testing for air leakage in single zone,

p.532constant volume, nonresidential air distribution systems serving zones with 5,000 ft2 of conditioned floor area or less.

p.532Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes