NA7.5.1.2.2 Functional Testing

p.5312025 Nonresidential Appendices (a) System is designed to provide a fixed minimum OSA when the unit is on.

p.531(b) Specify the method of delivering outside air to the unit.

p.531(c) Pre-occupancy purge has been programmed to meet the requirements of

p.531Standards §120.1(d)2.

p.531(d) Minimum position is marked on the outside air damper.

p.531(e) The system has means of maintaining the minimum outdoor air damper position.

p.531NA7.5.1.2.2 Functional Testing

p.531Step 1: If the system has an outdoor air economizer, force the economizer to the

p.531minimum position and stop outside air damper modulation (e.g., for a fixed drybulb high limit, lower the setpoint below the current outdoor air temperature).

p.531(a) Measured outside airflow reading is within 10 percent of the total ventilation air

p.531called for in the Certificate of Compliance.

p.531NA7.5.2 Constant-Volume, Single-Zone, Air Conditioners and Heat Pumps

p.531NA7.5.2.1 Construction Inspection

p.531Prior to Functional Testing, verify and document the following:

p.531(a) Thermostat is located as required by Standards §120.2(a).

p.531(b) Thermostat meets the temperature adjustment and dead band requirements of

p.531Standards §120.2(b).

p.531(c) Occupied, unoccupied, and holiday schedules have been programmed as

p.531specified by the facility’s schedule.

p.531(d) Pre-occupancy purge has been programmed to meet the requirements of

p.531Standards §120.1(d)2.

p.531NA7.5.2.2 Functional Testing

p.531Step 1: Disable economizer and demand control ventilation systems (if applicable).

p.531Step 2: Simulate a heating demand during the occupied condition. Verify and document

p.531the following:

p.531(a) Supply fan operates continually.

p.531(b) The unit provides heating.

p.531(c) No cooling is provided by the unit.

p.531(d) Outside air damper is at minimum position.

p.531Step 3: Simulate operation in the dead band during occupied condition. Verify and

p.531document the following:

p.531(e) Supply fan operates continually.

p.531(f) Neither heating nor cooling is provided by the unit.

p.531Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes