NA7.5.3.2.2 Diagnostic Apparatus

p.5342025 Nonresidential Appendices NA7.5.3.2.1 Instrumentation Specifications

p.534The instrumentation for the air distribution diagnostic measurements shall conform to the following specifications:

p.534(a) Pressure Measurements

p.534All pressure measurements shall be measured with measurement systems (i.e., sensor plus data acquisition system) having an accuracy of plus or minus 0.2 Pa. All pressure measurements within the duct system shall be made with static pressure probes, such as Dwyer A303 or equivalent.

p.534(b) Duct Leakage Measurements

p.534All measurements of duct leakage airflow shall have an accuracy of plus or minus 3 percent of measured airflow or better using digital gauges.

p.534(c) Calibration

p.534All instrumentation used for duct leakage diagnostic measurements shall be calibrated according to the manufacturer’s calibration procedure to conform to the accuracy requirement specified in Section NA7.5.3.2.1.

p.534NA7.5.3.2.2 Diagnostic Apparatus

p.534(a) Apparatus for Duct Pressurization and Leakage Flow Measurement

p.534The apparatus for duct system pressurization and duct system leakage measurements shall consist of a duct system pressurization and leakage airflow measurement device meeting the specifications in Section NA7.5.3.2.1.

p.534(b) Apparatus for Smoke-Test of Accessible-Duct Sealing (Existing Duct Systems)

p.534The apparatus for determining leakage in and verifying sealing of all accessible leaks in existing duct systems provide means for introducing controllable amounts of non-toxic visual or theatrical smoke into the duct pressurization apparatus for identifying leaks in accessible portions of the duct system. The means for generating smoke shall have sufficient capacity to ensure that any accessible leaks will emit visibly identifiable smoke.

p.534NA7.5.3.2.3 Verification and Diagnostic Procedures

p.534NA7.5.3.2.3.1 Nominal Air Handler Airflow

p.534Nominal air handler airflow shall be calculated according to one of the following methods:

p.534(a) For heating-only systems, the nominal air handler airflow shall be 21.7 CFM per

p.534kBtu/hr of rated heating output capacity.