NA7.5.15.1 Construction Inspection

p.5512025 Nonresidential Appendices (c) Storage/charge mode. Manually select storage mode. Verify that the TES system

p.551stores energy. If scheduled, input the time interval that would result in storage/charge mode. Verify that the TES system stores energy.

p.551(d) End of charge signal. Simulate a full storage charge by changing the

p.551(manufacturer recommended) thermal storage end of charge output sensor to the EMS. Verify that the storage charging has stopped.

p.551(e) Discharge mode. Generate a call for cooling. Manually select storage only

p.551discharge mode. Verify that the TES system starts discharging with the compressors off. Return to the off/secured mode. If scheduled, input the time interval that would result in discharge mode and verify that the storage starts discharging with the compressors off.

p.551(f) Mechanical cooling only mode. Generate a call for cooling. Manually select

p.551mechanical cooling only mode and verify that the storage does not discharge, and the cooling load is met by the compressor only. Return to the off/secure mode. If scheduled, input the time interval that would result in mechanical cooling only mode and verify that the storage does not discharge, and the cooling load is met by the compressor only.

p.551(g) Discharge and mechanical cooling mode. Generate a call for cooling. Manually

p.551select discharge and mechanical cooling mode and verify that the TES system discharges with the compressor sharing the load. If scheduled, input the time interval that would result in discharge and mechanical cooling mode and verify that the storage starts discharging with the compressor sharing the load.

p.551(h) Off/storage-secured mode. Manually select the off/storage-secured mode and

p.551verify that the storage does not discharge, and all compressors are off, regardless of the presence of calls for cooling. If scheduled, input the time interval that would result in off/storage-secured mode and verify that the storage does not discharge and all compressors are off, regardless of the presence of calls for cooling.

p.551(i) Charge plus cool mode. If provisions for this mode have been made by the system

p.551designer, verify that the tank(s) can be charged while serving an active cooling load, simulated by generating a call for cooling and entering the charge mode either manually or by time schedule. If the system disallows this mode of operation, verify that the energy storage is disallowed or discontinued while an active cooling load is present.

p.551NA7.5.15 Supply Air Temperature Reset Controls

p.551The following acceptance tests apply to supply air temperature reset controls.

p.551NA7.5.15.1 Construction Inspection

p.551Prior to functional testing, verify and document the following:

p.551(a) Supply air temperature reset controls are installed as specified by the

p.551requirements of the Section 140.4(f).

p.551Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes