NA7.5.15.2 Functional Testing

p.5522025 Nonresidential Appendices (b) All system air temperature sensors are factory or field calibrated within 2% of a

p.552calibrated reference temperature sensor. Attach a copy of the calibration certificate or field verification results.

p.552(c) Document current supply air temperature.

p.552NA7.5.15.2 Functional Testing

p.552(a) Check to make sure that chilled and hot water coils, if used, are not already fully

p.552open and calling for maximum cooling/heating. If this is the case, reverse Steps 1 and 2 and/or change the setpoint range as necessary to conduct this test.

p.552(b) Identify the reset controller parameter.

p.552Step 1: During occupied mode, adjust the reset control parameter to decrease the supply

p.552air temperature (to the lower supply temperature limit). Verify and document the following:

p.552(a) Supply air temperature controls modulate as intended.

p.552(b) Actual supply air temperature decreases to meet the new setpoint within ±2oF.

p.552(c) Supply air temperature stabilizes within 15 minutes.

p.552Step 2: During occupied mode, adjust the reset control parameter to increase the supply

p.552air temperature (to the upper supply temperature limit). Verify and document the following:

p.552(a) Supply air temperature controls modulate as intended.

p.552(b) Actual supply air temperature increases to meet the new setpoint within ±2oF.

p.552(c) Supply air temperature stabilizes within 15 minutes.

p.552Step 3: Restore reset control parameter to automatic control. Verify and document the

p.552following:

p.552(a) Supply air temperature controls modulate as intended.

p.552(b) Actual supply air temperature changes to meet the new setpoint within ±2oF.

p.552(c) Supply air temperature stabilizes within 15 minutes.

p.552NA7.5.16 Condenser Water Supply Temperature Reset Controls

p.552The following acceptance tests apply to condenser water temperature reset controls.

p.552NA7.5.16.1 Construction Inspection

p.552Prior to functional testing, verify and document the following:

p.552(a) Condenser water supply system, control system, and temperature control

p.552sequence, including condenser water supply high and low limits, are available and documented in the building documents.

p.552(b) Cooling tower fan motors are operational, and cooling tower fan speed controls

p.552(e.g., VSDs) are installed, operational, and connected to cooling tower fan motors