NA7.5.12.3 Functional Testing for Air Handling Unit Valves

p.5462025 Nonresidential Appendices NA7.5.12.3 Functional Testing for Air Handling Unit Valves

p.5472025 Nonresidential Appendices Step 4: Verify that the control system does not report a fault.

p.546(a) Bypass alarm delays

p.547(b) Damper/actuator fault:

p.5471. Damper stuck open.

p.546Step 1: If applicable, bypass alarm delays to ensure that faults generate alarms

p.546immediately.

p.547Step 1: Command the damper to be fully open (room temperature above setpoint).

p.546(b) Valve/actuator fault:

p.546Step 1: Override the operating state to occupied cooling mode by overriding zone

p.547Step 2: Disconnect the actuator to the damper.

p.546thermostat(s) to create a cooling demand and overriding the OAT sensor to 90oF.

p.547Step 3: Adjust the cooling setpoint so that the room temperature is below the cooling setpoint to command the damper to the minimum position. Verify that the control system reports a fault.

p.546Step 2: From the control system workstation, override the heating coil valves to the

p.546full open position (100 percent heating mode).

p.547Step 4: Reconnect the actuator and restore to normal operation.

p.546Step 3: Verify flow through the valve by differential temperature or differential

p.5472. Damper stuck closed.

p.546pressure method.

p.547Step 1: Set the damper to the minimum position.

p.546Step 4: Verify that a fault is reported at the control workstation.

p.547Step 2: Disconnect the actuator to the damper.

p.546Step 5: Remove the heating coil valve override and verify that the control system

p.547Step 3: Set the cooling setpoint below the room temperature to simulate a call for cooling. Verify that the control system reports a fault.

p.546indicates normal system operation.

p.546Step 6: Remove all overrides and clear all faults and alarms.

p.547Step 4: Reconnect the actuator and restore to normal operation.

p.546Step 7: Override the operating state to occupied heating mode by overriding zone

p.547(c) Valve/actuator fault (For systems with hydronic reheat):

p.546thermostat(s) to create a heating demand and overriding the OAT sensor to 40oF.

p.547Step 1: Command the reheat coil valve to (full) open.

p.546Step 8: From the control system workstation, override the cooling coil valve to the

p.547Step 2: Disconnect power to the actuator. Set the heating setpoint temperature to be lower than the current space temperature, to command the valve closed. Verify that the fault is reported at the control workstation.

p.546full open position (100 percent cooling mode).

p.546Step 9: Verify flow through the valve by differential temperature or differential

p.546pressure method.

p.547Step 3: Reconnect the actuator and restore normal operation.

p.546Step 10: Verify that a fault is reported at the control workstation.

p.547(d) Feedback loop tuning fault (unstable airflow):

p.546Step 11: Remove the cooling coil valve override and verify that the control system

p.547Step 1: Set the integral coefficient of the box controller to a value 50 times the current value.

p.546indicates normal system operation.

p.546Step 12: Remove all overrides and clear all faults and alarms.

p.547Step 2: The damper cycles continuously and airflow is unstable. Verify that the control system detects and reports the fault.

p.546(c) Reinstate alarm delay.

p.547Step 3: Reset the integral coefficient of the controller to the original value to restore normal operation.

p.546Step 1: Reinstate alarm delays to ensure that faults generate alarms as before

p.546Step (a), if applicable.

p.547(e) Disconnected inlet duct:

p.546NA7.5.12.4 Functional Testing for Zone Terminal Units

p.547Step 1: From the control system workstation, commands the damper to full closed, then disconnect power to the actuator and verify that a fault is reported at the control workstation.

p.546Testing shall be performed on one of each type of terminal unit (VAV box) in the project. A minimum of 5 percent of the terminal boxes shall be tested.

p.546(a) Sensor drift/failure:

p.547(f) Discharge air temperature sensor:

p.546Step 1: Disconnect the tubing to the differential pressure sensor of the VAV box.

p.547Step 1: Adjust zone setpoints to drive the box from dead band to full heating.

p.546Step 2: Verify that control system detects and reports the fault.

p.547Step 2: Verify that in heating, the supply air temperature resets up to the maximum setpoint while the airflow is maintained at the dead band flow rate.

p.546Step 3: Reconnect the sensor and verify proper sensor operation.

p.546Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.547

p.547Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes