p.5442025 Nonresidential Appendices NA7.5.11.2.3Functional Testing for Economizer Operation
p.5452025 Nonresidential Appendices Step 1: Override the operating state to occupied heating mode by overriding zone thermostat(s) to create a heating demand and overriding the OAT sensor below the low limit lockout.
p.544Step 1: Interfere with normal unit operation so test NA7.5.4 Air Economizer Controls fails
p.544by immobilizing the outdoor air economizer damper according to manufacturer’s instructions.
p.545Step 2: From the control system workstation, override the economizer dampers to 100 percent outdoor air.
p.544(a) After NA7.5.4 Air Economizer Controls fails, verify FDD system reports a fault.
p.545Step 3: Verify that a fault is reported at the control workstation.
p.544Step 2: Successfully complete and pass NA7.5.4 Air Economizer Controls.
p.545Step 4: Remove the economizer damper override and verify that the control system indicates normal system operation.
p.544(b) After NA7.5.4 Air Economizer Controls passes, verify FDD system reports normal
p.544operation.
p.545Step 5: Remove all overrides and clear all faults and alarms.
p.544NA7.5.12 Automatic Fault Detection and Diagnostics (FDD) for Air Handling Units and Zone Terminal Units.
p.545Step 6: Override the operating state to economizer-only cooling mode by overriding zone thermostat(s) to create a cooling demand and overriding the OAT sensor so that free cooling is available.
p.544NA7.5.12.1 Construction Inspection for Air Handling Units
p.545Step 7: From the control system workstation, override the economizer dampers to 0 percent outdoor air.
p.544Prior to Functional Testing, verify and document the following:
p.544a) Verify on the submittal documents or sensor specifications that locally installed
p.545Step 8: Verify that a fault is reported at the control workstation.
p.544supply air, outside air, and return air (if applicable) temperature sensors have an accuracy of ±2oF over the range of 40oF to 80oF.
p.545Step 9: Remove the economizer damper override and verify that the control system indicates normal system operation.
p.545Step 10: Remove all overrides and clear all faults and alarms.
p.544NA7.5.12.2 Functional Testing for Air Handling Unit Economizers
p.545(d) Reinstate alarm delay.
p.544Testing of each AHU with FDD controls shall include the following tests.
p.545Step 1: Reinstate alarm delays to ensure that faults generate alarms as before step
p.544(a) Bypass alarm delays.
p.545(a), if applicable.
p.544Step 1: If applicable, bypass alarm delays to ensure that faults generate alarms immediately.
p.544(b) Sensor failure:
p.544Step 1: Disconnect local supply air temperature sensor from unit controller.
p.544Step 2: Verify that the FDD system reports a fault.
p.544Step 3: Connect SAT sensor to the unit controller.
p.544Step 4: Verify that FDD indicates normal system operation and clear all faults and alarms.
p.544Step 5: If the outside air temperature sensor is local, disconnect the local OAT from the unit controller.
p.544Step 6: Verify that the FDD system reports a fault.
p.544Step 7: Connect the local OAT sensor to the unit controller.
p.544Step 8: Verify that FDD indicates normal system operation and clear all faults and alarms.
p.544(c) Inappropriate economizing:
p.544Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.545
p.545Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes