p.172JA5.1 Introduction
p.172Joint Appendix 5 (JA5) provides the technical specifications for an Occupant Controlled Smart Thermostat (OCST). An OCST can be an independent device or part of a control system comprised of multiple devices.
p.172The requirements in this appendix are intended to be compatible with National Electrical Manufacturers Association (NEMA) Standard DC 3-2013 Residential Controls – Electrical Wall Mounted Thermostats and NEMA DC 3 Annex A-2013 Energy-Efficiency Requirements for Programmable Thermostats.
p.172JA5.1.1 Manufacturer Self-Certification
p.172An OCST is compliant with Title 24, Part 6, only if it has been certified to the Energy Commission as meeting all of the requirements in this Appendix. Certification to the Energy Commission shall be as specified in Section 110.0.
p.172JA5.2 Required Functional Specification
p.172JA5.2.1 Setback Capabilities
p.172An OCST shall meet the requirements of Section 110.2(c). Thermostats for heat pumps shall also meet the requirements of Section 110.2(b).
p.172JA5.2.2 Restart Settings
p.172In the event of a disruption of power to the device that results in power off or restart, upon device restart, the device shall automatically restore the most recently programmed settings, including reconnection to a network, if the device was previously enabled and network connectivity is available.
p.172JA5.2.3 Automatic Rejoin
p.172An OCST shall connect and remain connected in its communication path and control end point. The OCST shall incorporate an automatic rejoin function. When physical and/or logical communication is lost, the OCST shall trigger its automatic rejoin function to restore the physical and/or logical communication.
p.172JA5.2.4 Event Responses
p.172Event response, unless overridden by the occupant or modified by an energy management control system or service, may be triggered by price signals or Demand Response Signals. The OCST shall provide one set of event responses for price signals and one set of event responses for Demand Response Signals. The responses may be common for both types of events. The OCST’s default responses shall comply with the following:
p.172Appendix JA5 – Technical Specifications for Demand Responsive Thermostatsp.173
p.173(a) A Demand Response Signal shall trigger the OCST to adjust the thermostat
p.173setpoint by either the default number of degrees or the number of degrees established by the occupant.
p.173(b) When a price signal indicates a price in excess of a price threshold established by
p.173the occupant, the OCST shall adjust the thermostat setpoint by either the default number of degrees or the number of degrees established by the occupant.
p.173(c) In response to price signals or Demand Response signals, the OCST shall default
p.173to an event response that initiates setpoint offsets of +4°F for cooling and -4°F for heating relative to the current setpoint.
p.173(d) The OCST shall have the capability to allow occupants or their representative to
p.173modify the default event response with occupant defined event responses for cooling and heating relative to the current setpoint in response to price signals or Demand Response Signals.
p.173(e) Override Function: Occupants shall be able to change the event responses and
p.173thermostat settings or setpoints at any time, including during price events or Demand Response Periods.
p.173(f) The Demand Response Signal shall start the Demand Response Period either
p.173immediately or at a specific start time as specified in the event signal and continue for the Demand Response Period specified in the Demand Response Signal or until the occupant overrides the event setpoint.
p.173(g) The thermostat’s price response shall start either immediately or at a specific start
p.173time as specified in the pricing signal and continue for the duration specified in the pricing signal or until the occupant overrides the event setpoint.
p.173(h) The OCST shall have the capability to allow occupants to define setpoints for
p.173cooling and heating in response to price signals or Demand Response signals as an alternative to the default event response.
p.173(i) At the end of a price event or Demand Response Period, the thermostat setpoint
p.173shall be set to the setpoint that is programmed for the point in time that the event ends or to the manually established setpoint that existed just prior to the Demand Response Period.
p.173The OCST shall include the capability to allow the occupant to restore the factory installed default settings.