NA7.6.1 Daylight Responsive Controls Acceptance Tests

Figure on PDF page 557
p.557 Needs alt text review

p.557NA7.6.1 Daylight Responsive Controls Acceptance Tests

p.557NA7.6.1.1 Construction Inspection

p.557Prior to Functional testing, verify and document the following:

p.557(a) The daylit zones are shown on plans documents.

p.557(b) The general lighting in skylit daylit zones, primary sidelit daylit zones and

p.557secondary sidelit daylit zones is controlled by daylighting responsive controls. In parking garages, the general lighting in the combined primary and secondary sidelit daylit zones is controlled by daylighting responsive controls.

p.557(c) The daylighting responsive controls provide separate control for luminaires in each

p.557type of daylit zone. General lighting in overlapping skylit daylit zone and a sidelit daylit zone are controlled as part of the skylit zone. General lighting in both a primary sidelit daylit zone and secondary sidelit daylit zone are controlled as part of the primary sidelit daylit zone.

p.557(d) All photosensors are not readily accessible to unauthorized personnel.

p.557NA7.6.1.2 Functional Testing - Sampling

p.557All photocontrols serving more than 5,000 ft2 of daylit area shall undergo functional testing. Photocontrols that are serving smaller spaces may be sampled as follows:

p.557For buildings with up to five (5) photocontrols, all photocontrols shall be tested. For buildings with more than five (5) photocontrols, sampling may be done on spaces with similar sensors and cardinal orientations of glazing; sampling shall include a minimum of one (1) photocontrol for each group of up to five (5) additional photocontrols. If the first photocontrol in the sample group passes the functional test, the remaining photocontrols in the sample group also pass. If the first photocontrol in the sample group fails the functional test, the rest of the photocontrols in the group shall be tested. If any tested photocontrol fails the functional test, it shall be repaired, replaced, or adjusted until it passes the test.

p.557For each photocontrol to be tested, test each group of lights controlled separately by the photocontrol according to the protocol in NA7.6.1.4 and NA7.6.1.5. In all interior spaces other than parking garages, separate tests are conducted for daylighting control of the primary sidelit daylit zone and for daylight control of the secondary sidelit daylit zone. In parking garages, the tests are conducted on daylighting controls that control the combined area of the primary and secondary sidelit daylit zone.

p.557NA7.6.1.3 RESERVED

p.557NA7.6.1.4 Continuous Dimming Control Systems Functional Testing

p.557Continuous dimming control systems provide more than 10 levels of controlled light output per zone.

p.557Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.558

p.5582025 Nonresidential Appendices (a) Reference Location. Identify the minimum daylight location in the controlled zone

p.558(Reference Location) for each daylit zone type (skylit, primary sidelit, and secondary sidelit) in the space. This can be identified using either the illuminance method or the distance method and will be used for illuminance measurements in subsequent tests. For parking garages, the reference location should always be the farthest edge of the secondary sidelit daylit zone away from the opening or glazing.

p.558Illuminance Method

p.558The Reference Location is the task location with lowest daylight illuminance in the zone illuminated by controlled luminaires.

p.558Turn off controlled lighting and measure daylight illuminance within zones illuminated by controlled luminaires. (Note: turn the controlled lighting back on before proceeding to the No Daylight Test)

p.558Distance Method

p.558The Reference Location is the task location within the zone illuminated by controlled luminaires that is farthest away from daylight sources.

p.558(b) No Daylight Test. Simulate or provide conditions without daylight. Verify and

p.558document the following:

p.5581. Document the reference illuminance at the Reference Location, which is the electric lighting illuminance level at the Reference Location.

p.5582. Daylight responsive control system turns on all controlled lighting to full light output (full design output, or full programmed output) unless it has been documented, such as in design documents, that continuous dimming luminaires have been intentionally tuned to less than full light output.

p.5583. Light output is stable with no visible flicker.

p.558(c) Full Daylight Test. Simulate or provide bright conditions where the daylight

p.558illuminance is greater than 150 percent of the reference illuminance (measured during the No Daylight Test). Alternatively, provide simulated bright conditions by shining a bright light into the daylight sensor. Verify and document the following:

p.5581. The controlled lighting power reduction is at least 90 percent under fully dimmed conditions for non-parking garage locations. For parking garages, the controlled lighting power reduction is 100 percent under fully dimmed conditions.

p.5582. Only luminaires in daylit zones are affected by daylight control. If the daylighting control system controls luminaires outside of the daylight zones including those behind obstructions, the control system is not compliant.

p.5583. If a Power Adjustment Factor (PAF) is claimed for daylight continuous dimming plus off controls in accordance with Section 140.6(a)2H; a compliant system shall automatically turn off the luminaires in order to pass the Full Daylight Test for daylight continuous dimming plus off controls. This portion of the Full Daylight Test does not apply to lighting systems that are not claiming a PAF for daylight continuous dimming plus off controls.

p.558Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.559

p.5592025 Nonresidential Appendices (d) Partial Daylight Test. Simulate or provide daylight conditions where illuminance

p.559provided only by daylight only at the Reference Location is between 60 and 95 percent of Reference Illuminance measured during the No Daylight Test. Verify and document the following:

p.5591. Measure that the combined daylight and controlled electric lighting illuminance at the Reference Location is no less than the reference illuminance measured at this location during the No Daylight Test.

p.5592. Verify that the combined daylight and controlled electric lighting illuminance at the Reference Location is no greater than 150 percent of the reference illuminance.

p.5593. Light output is stable with no visible flicker.

p.559(Note: only luminaires in daylit zones are affected by daylight control)

p.559(e) Alternate Partial Daylight Test. When outdoor horizontal illuminance is at least 4,000 fc and where illuminance from daylight only at the Reference Location (Partial Daylight Illuminance) is no greater than 80 percent of Reference Illuminance measured at this location during the No Daylight Test. Measure the outdoor horizontal illuminance level and the daylight illuminance level, and do not proceed until the illuminance criteria are met.

p.559Verify and document the following:

p.5591. Measure the Partial Daylight Illuminance at the Reference Location. This can be measured by turning the electric lighting off. (Turn the electric lighting back on before proceeding to next step.)

p.5592. Measure the combined daylight and controlled electric lighting at the Reference Location.

p.5593. This alternate partial daylight test is passed if the measured illuminance value (from Step 2) is no less than the Reference Illuminance measured at this location during the no daylight test and no greater than Partial Daylight Combined Illuminance Maximum (PDCIM).

p.559In other words, the measured value must be within the following range in order to pass this test.

p.559Reference Illuminance (from the no daylight test) ≤ measured illuminance value (from Step 2) ≤ PDCIM,

p.559where PDCIM = Reference Illuminance (from the no daylight test) + 0.40 x Daylight Illuminance (from Step 1).

p.5594. Light output is stable with no visible flicker.

p.5595. Only luminaires in daylit zones are affected by daylight control.