NA7.18.1 Dwelling Unit Ventilation System Acceptance

p.600Multifamily Building Acceptance Tests

Figure on PDF page 600
p.600 Needs alt text review

p.600NA7.18.1 Dwelling Unit Ventilation System Acceptance

p.600NA7.18.1.1 Dwelling Unit Ventilation Acceptance

p.600NA7.18.1.1.1Construction Inspection

p.600Prior to functional testing, verify and document the following:

p.600a) System is designed to provide the required outside air when the unit is operating.

p.600b) Specify the ventilation system type, such as balanced, supply or exhaust.

p.600c) Specify the method of control.

p.600d) Confirm the kitchen range hood is ventilated to outside.

p.600e) Record the kitchen range hood manufacturer name and equipment model number.

p.600f) Confirm the kitchen range hood is HVI certified to perform in compliance.

p.600g) Confirm HRV or ERV equipment is HVI certified to perform in compliance.

p.600Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.601

p.6012025 Nonresidential Appendices NA7.18.1.1.2Functional Testing