RA3.9.1 Purpose and Scope

p.438RA3.9.1 Purpose and Scope

p.438RA3.9 contains procedures for measurement of WHF systems in single-family buildings:

p.438(a) Measurement of WHF airflow rate to confirm compliance with the airflow rate

p.438requirements specified in the performance standards set forth in Standards section 150.1(b).

p.438(b) Measurement of WHF Watt draw.

p.438(c) Calculation of WHF efficacy (w/cfm) utilizing simultaneous measurement of WHF Watt

p.438draw and airflow rate.

p.438RA3.9.2 Instrument Specifications

p.438The instrumentation for the diagnostic measurements shall conform to the following specifications:

p.438RA3.9.2.1 Pressure Measurement

p.438All pressure measurements shall be performed with measurement systems (i.e., sensor plus data acquisition system) having an accuracy of ± 1% of pressure reading or ± 0.2 Pa (.0008 inches water) (whichever is greater).

p.438RA3.9.2.2 Airflow Rate Measurements

p.438All measurements of WHF airflow rates shall be made with an airflow rate measurement apparatus (i.e., sensor plus data acquisition system) having an accuracy of ± 7% of reading or ± 5 cfm whichever is greater.

p.438RA3.9.2.3 Fan Watt Draw Measurements

p.438All measurements of WHF watt draws shall be made with true power measurement systems (i.e., sensor plus data acquisition system) having an accuracy of ± 2% of reading or ± 10 watts whichever is greater.

p.438RA3.9.3 WHF Airflow Rate Measurement Apparatus

p.438WHF airflow rate shall be measured using one of the apparatuses listed in Section RA3.9.3. The apparatus shall produce airflow rate measurements that conform to the accuracy requirements specified in Section RA3.9.2 for measurements of residential WHFs.

p.438The airflow rate measurement apparatus manufacturers shall publish in their product documentation, specifications for how their airflow measurement apparatuses are to be used for accurately measuring WHF airflow rates.

p.438The airflow measurement apparatus manufacturers shall certify to the Energy Commission that use of the apparatus in accordance with the specifications given in the manufacturer's product documentation will produce measurement results that are within the accuracy required by Section RA3.9.2.

p.438– Residential Field Verification and Diagnostic Test Protocolsp.439

p.4392025 Residential Appendices For the airflow measurement apparatuses that are certified to the Commission as meeting the accuracy required by Section RA3.9.2, the following information will be posted on the Energy Commission website, making the information available to all people involved in the airflow verification compliance process:

p.439(a) The product manufacturers' model numbers for the airflow measurement apparatuses.

p.439(b) The product manufacturers' product documentation that gives the specifications for use of

p.439the airflow measurement apparatuses to accurately measure WHF airflow.

p.439A manufacturer's certification to the Commission of the accuracy of the airflow measurement apparatus, and submittal to the Commission of the product documentation that specifies the proper use of the airflow measurement apparatus to produce accurate airflow rate measurements shall be prerequisites for allowing the manufacturer's airflow measurement apparatus to be used for conducting the system airflow verification procedures in Section RA3.9 for demonstrating compliance with Part 6.