Residential Appendix RA4
p.445Appendix RA4 – Eligibility Criteria for Energy Efficiency Measures
p.445RA4.1 Purpose and Scope
p.445This appendix contains the eligibility requirements which must be met when any of the following features are installed to achieve compliance with the residential building energy efficiency standards. Building Envelope Measures.
p.445RA4.2 Envelope Measures
p.445RA4.2.1 Radiant Barriers
p.445Radiant barriers shall meet specific eligibility and installation criteria to be modeled by any compliance software and receive energy credit for compliance with the Building Energy Efficiency Standards for low-rise residential buildings.
p.445The emittance of the radiant barrier shall be less than or equal to 0.05 as tested in accordance with ASTM C1371 or ASTM E408.
p.445Installation shall conform to ASTM C1158 (Standard Practice for Installation and Use of Radiant Barrier Systems (RBS) in Building Construction), ASTM C727 (Standard Practice for Installation and Use of Reflective Insulation in Building Constructions), ASTM C1313 (Standard Specification for Sheet Radiant Barriers for Building Construction Applications), and ASTM C1224 (Standard Specification for Reflective Insulation for Building Applications), and the radiant barrier shall be securely installed in a permanent manner with the shiny side facing down toward the interior of the building (ceiling or attic floor). Moreover, radiant barriers shall be installed at the top chords of the roof truss/rafters in any of the following methods:
p.445(a) Draped over the truss/rafter (the top chords) before the upper roof decking is installed.
p.445(b) Spanning between the truss/rafters (top chords) and secured (stapled) to each side.
p.445(c) Secured (stapled) to the bottom surface of the truss/rafter (top chord). A minimum air
p.445space shall be maintained between the top surface of the radiant barrier and roof decking of not less than 1.5 inches at the center of the truss/rafter span.
p.445(d) Attached [laminated] directly to the underside of the roof decking. The radiant barrier
p.445shall be laminated and perforated by the manufacturer to allow moisture/vapor transfer through the roof deck.
p.445(e) In addition, the radiant barrier shall be installed to cover all gable end walls and other
p.445vertical surfaces in the attic.
p.445– Eligibility Criteria for Energy Efficiency Measuresp.446
p.4462025 Residential Appendices RA4.2.1.1 For Prescriptive Compliance: The attic shall be ventilated to: