p.577The measurement devices used to verify the refrigerated warehouse controls shall be calibrated once every two years using a NIST traceable reference. The calibrated measurement devices to be used in these acceptance tests are called the "standard" and shall have the following measurement tolerances: The temperature measurement devices shall be calibrated to +/- 0.7°F between -30°F and 200°F. The pressure measurement devices shall be calibrated to +/- 2.5 psi between 0 and 500 psig. The relative humidity (RH) measurement devices shall be calibrated to +/- 1% between 5% and 90% RH.
p.577NA7.10.1 Electric Resistance Underslab Heating System
p.577NA7.10.1.1 Construction Inspection
p.577Prior to functional testing, verify and document the following for all electric resistance underslab heating systems:
p.577(a) Verify that summer on-peak period is programmed into all underslab heater
p.577controls to meet the requirements of Section 120.6(a)2.
p.577NA7.10.1.2 Functional Testing
p.577Step 1: Using the control system, lower slab temperature setpoint. Verify and document
p.577the following using an electrical test meter:
p.577(a) The underslab electric resistance heater is off.
p.577Step 2: Using the control system, raise the slab temperature setpoint. Verify and document the following using an electrical test meter:
p.577(b) The underslab electric resistance heater is on.
p.577Step 3: Using the control system, change the control system’s time and date
p.577corresponding to the local utility’s summer on-peak period. If control system only accounts for time, set system time corresponding to the local utility’s summer on- peak period. Verify and document the following using an electrical test meter:
p.577(c) The underslab electric resistance heater is off.
p.577Step 4: Restore system to correct schedule and control setpoints.
p.577NA7.10.2 Evaporators and Evaporator Fan Motor Variable Speed Control
p.577NA7.10.2.1 Construction Inspection
p.577Prior to functional testing, document the following on all evaporators:
p.577(a) All refrigerated space temperature sensors used for control are verified to read
p.577accurately (or provide an appropriate offset) using a temperature standard.
p.577(b) All refrigerated space humidity sensors used for control are verified to read
p.577accurately (or provide an appropriate offset) using a humidity standard.
p.577Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.578
p.5782025 Nonresidential Appendices (c) All refrigerated space temperature and humidity sensors are verified to be
p.578mounted in a location away from direct evaporator discharge air draft.
p.578(d) Verify that all fan motors are operational and rotating in the correct direction.
p.578(e) Verify that fan speed control is operational and connected to evaporator fan
p.578motors.
p.578(f) Verify that all speed controls are in “auto” mode.