Appendix RA3 – Residential Field Verification and Diagnostic Test Protocols

Figure on PDF page 323
Text in this figure

Residential Appendix RA3

p.323 Needs alt text review

p.323Appendix RA3 – Residential Field Verification and Diagnostic Test Protocols

p.323RA3.1 Field Verification and Diagnostic Testing of Air Distribution Systems

p.323RA3.1.1 Purpose and Scope

p.323RA3.1 contains procedures for measuring the air leakage in forced air distribution systems as well as procedures for verifying duct location, duct surface area, duct R-value, return duct design, return grille design, and air filter installation.

p.323RA3.1 applies to air distribution systems in both new and existing single-family and multifamily residential buildings.

p.323RA3.1 provides required procedures for installers, ECC-raters and others who are required to perform field verification of air distribution systems.

p.323Table RA3.1-1 is a summary of the tests and criteria included in RA3.1.

p.323Table RA3.1-2 Provides compliance criteria for the duct leakage test protocols in Section RA3.1.4.3.

p.323Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.324

p.3242025 Residential Appendices

p.324Verification/Diagnostic Description Procedure

p.324Verify duct system was installed according to the specifications on the Certificate of Compliance or in accordance with an approved duct system design layout.

p.324RA3.1.4.1

p.324Duct Location, Surface Area and R-value

p.324Verified Duct System Design

p.324Procedure for duct system design layout approval and field verification

p.324RA3.1.4.1.1

p.324Duct Leakage Verify that duct leakage is less than or equal to the compliance criteria given in Table RA3.1-2.

p.324RA3.1.4.3

p.324Return Duct Design Verify compliance with the return duct and return grill sizing requirements of Table 150.0-B or Table 150.0-C).

p.324RA3.1.4.4

p.324Air Filter Device Design Verify compliance with the requirements in 150(m)12. RA3.1.4.5

p.324Verification of Prescriptive Bypass Duct Requirements

p.324Verification to confirm zonally controlled systems comply with the bypass duct requirements in 150.1(c)13

p.324RA3.1.4.6

p.324Verification of Space- Conditioning System Airflow Supply to All Habitable Spaces

p.324Verify that all habitable spaces in the dwelling unit receive space-conditioning system airflow.

p.324RA3.1.4.1.7

p.324Verification of Ductless Space-Conditioning System Indoor Units Located Entirely in Conditioned Space

p.324Verify that ductless indoor units are located entirely in conditioned space.

p.324RA3.1.4.1.8