RA3.7 Field Verification and Diagnostic Testing of Mechanical Ventilation Systems

p.430RA3.7 Field Verification and Diagnostic Testing of Mechanical Ventilation Systems

p.430RA3.7.1 Purpose and Scope

p.430RA3.7 contains procedures for verification of heat recovery efficiency and fan efficacy, and for measuring the airflow rate for mechanical ventilation systems.

p.430RA3.7 is applicable to mechanical ventilation systems in residential dwelling units.

p.430RA3.7 provides required procedures for installers, ECC-raters and others who are required to perform field verification of mechanical ventilation systems for compliance with Part 6.

p.430Table RA3.7-1 – Summary of Verification and Diagnostic procedures

DiagnosticDescriptionProcedure
Whole-Building Mechanical Ventilation AirflowVerification of whole-building ventilation system airflow rate. Continuous OperationRA3.7.4.1
Whole-Building Mechanical Ventilation AirflowVerification of whole-building ventilation system airflow rate. Intermittent OperationRA3.7.4.2
Kitchen Local Mechanical ExhaustVerification of vented range hood airflow rate or capture efficiencyRA3.7.4.3

p.430– Residential Field Verification and Diagnostic Test Protocolsp.431

p.4312025 Residential Appendices Diagnostic Heat Recovery Ventilation (HRV) or

p.431Description Verification of the HRV/ERV fan efficacy (W/cfm) or heat recovery

p.431Procedure

p.431RA3.7.4.4

p.431Energy Recovery Ventilation (ERV) Rated

p.431efficiency.

p.431Performance

p.431Verification