NA6.4 Default Visible Transmittance, VT

Figure on PDF page 516
p.516 Needs alt text review

p.516Equation NA6-3 - VT of Center of Glass (COG) calculation

p.516VTT = VTF x VTC

p.516Where:

p.516VTT = Is the Total Performance of the fenestration including glass and frame

p.516VTF = 0.53 for projecting windows, such as casement and awning windows

p.516VTF = 0.67 for operable or sliding windows

p.516VTF = 0.77 for fixed or non-operable windows

p.516VTF= 0.88 for curtain wall/storefront, Site-built and manufactured non-curb mounted skylights

p.516VTF = 1.0 for Curb Mounted manufactured Skylights

p.516VTC = Center of glass VT is calculated in accordance with NFRC 200 Section 4.5.1.1 or NFRC 202 for Translucent Products or NFRC 203 for Tubular Daylighting Devices and Hybrid Tubular Daylighting Devices or ASTM E972 (http://www.nfrc.org/software.aspx)

p.516Responsibilities for Compliance

Figure on PDF page 516
p.516 Needs alt text review

p.516This section describes the responsibilities of energy consultants, designers, architects, builders, installers, and enforcement agencies when using the procedures of this appendix.

p.516NA6.5.1 Energy Consultants, Designers, Architects

p.516The person with responsibility for preparing the compliance documentation shall establish the inputs from the following:

p.516(a) The center of glass U-factor, SHGC and VT shall be taken from manufacturers’

p.516literature and determined using methods consistent with NFRC 100, NFRC 200, NFRC 202 and NFRC 203 procedures.

p.516(b) The frame type (Metal, Metal Thermal Break, Non-metal) shall be verified from

p.516manufacturers’ literature and through observations of frame sections provided by the manufacturer.

p.516For the Prescriptive Overall Compliance Method, the calculated values shall be entered on the prescriptive Certificate of Compliance form. In addition, the Fenestration Certificate of Compliance Label Certificate must be also filled and located at the project site location in according to Reference Nonresidential Appendix NA7.

p.516For the Performance Compliance Approach, the calculated values shall be entered and documented on the Performance Certificates of Compliance. In addition, the Fenestration Certificate of Compliance Label Certificate must be filled and located at the project site location in according to Reference Nonresidential Appendix NA7.

p.516Appendix NA6– Alternate Default Fenestration Procedure to Calculate Thermal Performancep.517

p.5172025 Nonresidential Appendices For both the prescriptive and performance compliance method, the building plans shall contain a window schedule that lists the calculated values in which matches the Fenestration Certificate of Compliance form or improved thermal performance values than listed on the Fenestration Certificate of Compliance form. The specifications of the windows shall be consistent with the values used in this procedure, e.g., frame type glazing product, etc.

p.517Permit applications must include fenestration U-factor, SHGC and VT values documentation for the building plan checker. This documentation must include a copy of the manufacturer’s documentation showing the Glazing Type information (center of glass U-factor, center of glass SHGC, center of glass VT, number of panes, coatings, and the frame type (frame material type, presence of thermal breaks, and identification of structural glazing (glazing with no frame)) that is used to determine UT, SHGCT, and VTT. If the proposed design uses multiple fenestration products, manufacturer’s documentation for each fenestration product shall be attached to the plans. Manufacturer’s documentation must be provided for each unique combination of glazing and frame used for compliance and shall be located at the project's location.

p.517If mixed fenestration is included in the compliance analysis, then the compliance submittal must clearly identify which are certified fenestration products, and which are non-certified fenestration products. In nonresidential buildings, non-certified fenestration products are limited to 200 ft2 of skylight area and altered vertical fenestration. In residential buildings, non-certified fenestration products are limited to 250 ft2 in area, or 0.5% of the CFA, whichever is greater.

p.517The manufacturer’s documentation and calculations for each product must be included in the submittal, and either the Prescriptive Certificate of Compliance or Performance Certificate of Compliance form must be included on the building plans. All non-certified fenestration products, including skylights, require a completed Fenestration Certificate of Compliance.