p.611The following tables contain a limited list of lamp and ballast combinations. These tables provide an alternate voluntary option to the provision in Section 130(c) for determining luminaire power for any lamp and ballast combination specifically listed in Appendix NA8. This appendix is not intended to list all possible lamp and ballast combinations, and shall not to be used to determine luminaire power for any lighting system not specifically listed in this appendix.

p.611Table NA8-1 – Fluorescent U-Tubes

TypeLamps - NumberLamps ­ DesignationBallasts - NumberBallasts ­ DesignationBallasts ­ DescriptionSystem Watts
2 ft. Fluorescent U-Tube T81FB31T8/F32T8U1ELECT NOElectronic Normal Output39
2 ft. Fluorescent U-Tube T82FB31T8/F32T8U1ELECT NOElectronic Normal Output62
2 ft. Fluorescent U-Tube T83FB31T8/F32T8U1ELECT NOElectronic Normal Output92
2 ft. Fluorescent U-Tube T81FB31T8/F32T8U1ELECT DIMElectronic Dimming33
2 ft. Fluorescent U-Tube T82FB31T8/F32T8U1ELECT DIMElectronic Dimming64
2 ft. Fluorescent U-Tube T83FB31T8/F32T8U1ELECT DIMElectronic Dimming93
2 ft. Fluorescent U-Tube T84FB31T8/F32T8U1ELECT DIMElectronic Dimming116
NO = ballastfactor 85 to100%

p.611Appendix NA8 –Luminaire Powerp.612

p.6122025 Nonresidential Appendices

p.612Appendix NA8 –Luminaire Powerp.613

p.6132025 Nonresidential Appendices

TypeLamps - Lamps NumberDesignationBallasts ­ NumberBallasts ­ DesignationBallasts - DescriptionSystem Watts
~23” Fluorescent Program Start T5 (14W)1F14T51ELECTElect. Program Start BF=118
~23” Fluorescent Program Start T5 (14W)2F14T51ELECTElect. Program Start BF=134
~34.5” Fluorescent Program Start T5 (21W)1F21T51ELECTElect. Program Start BF=127
~34.5” Fluorescent Program Start T5 (21W)2F21T51ELECTElect. Program Start BF=150
~46” Fluorescent Program Start T5 (28W)1F28T51ELECTElect. Program Start BF=130
~46” Fluorescent Program Start T5 (28W)2F28T51ELECTElect. Program Start BF=160
~58.5” Fluorescent Program Start T5 (35W)1F35T51ELECTElect. Program Start BF=140
~58.5” Fluorescent Program Start T5 (35W)2F35T51ELECTElect. Program Start BF=178
~23” Fluorescent Program Start T5 High Output (24W)1F24T5HO1ELECTElect. Program Start BF=129
~23” Fluorescent Program Start T5 High Output (24W)2F24T5HO1ELECTElect. Program Start BF=155
~34.5” Fluorescent Program Start T5 High Output(39W)1F39T51ELECTElect. Program Start BF=143
~34.5” Fluorescent Program Start T5 High Output(39W)2F39T51ELECTElect. Program Start BF=185
~46” Fluorescent Program Start T5 High Output (54W)1F54T51ELECTElect. Program Start BF=162
~46” Fluorescent Program Start T5 High Output (54W)2F54T51ELECTElect. Program Start BF=1121
TypeLamps - Lamps NumberDesignationBallasts ­ NumberBallasts ­ DesignationBallasts - DescriptionSystem Watts
~46” Fluorescent Program Start T5 High Output (54W)1F54T51ELECT DIMElect. Dimming63
~46” Fluorescent Program Start T5 High Output (54W)2F54T51ELECT DIMElect. Dimming125
~57.5” Fluorescent Program Start T5 High Output (80W)1ºF80T51ELECTElect. Program Start BF=190

p.613Appendix NA8 –Luminaire Powerp.614

p.6142025 Nonresidential Appendices

p.614Appendix NA8 –Luminaire Powerp.615

p.6152025 Nonresidential Appendices

Table NA8-3 – FluorescentRapidStart T-8
TypeLamps - NumberLamps ­ DesignationBallasts NumberBallasts ­ DesignationBallasts ­ DescriptionSystem Watts
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts1F17T81ELECT NOElectronic Normal Output22
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts2F17T81ELECT NOElectronic Normal Output33
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts3F17T81ELECT NOElectronic Normal Output53
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts3F17T82ELECT NOElectronic Normal Output55
2 foot Fluorescent Rapid Start T8 (17W) Electronic Ballasts4F17T81ELECT NOElectronic Normal Output63
2 foot Fluorescent Rapid Start T8 (17W)1F17T81ELECT DIMElectronic Dimming20
2 foot Fluorescent Rapid Start T8 (17W)2F17T81ELECT DIMElectronic Dimming37
2 foot Fluorescent Rapid Start T8 (17W)3F17T81ELECT DIMElectronic Dimming56
2 foot Fluorescent Rapid Start T8 (17W)4F17T81ELECT DIMElectronic Dimming69
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts1F25T81ELECT NOElectronic Normal Output27
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts2F25T81ELECT NOElectronic Normal Output48
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts3F25T81ELECT NOElectronic Normal Output68
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts4F25T81ELECT NOElectronic Normal Output89
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts1F25T81ELECT ROElectronic Reduced Output24
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts2F25T81ELECT ROElectronic Reduced Output41

p.615Appendix NA8 –Luminaire Powerp.616

p.6162025 Nonresidential Appendices

TypeLamps - NumberLamps ­ DesignationBallasts NumberBallasts ­ DesignationBallasts ­ DescriptionSystem Watts
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts3F25T81ELECT ROElectronic Reduced Output59
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts4F25T81ELECT ROElectronic Reduced Output76
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts1F25T81ELECT HOElectronic High Output29
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts2F25T81ELECT HOElectronic High Output51
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts3F25T81ELECT HOElectronic High Output74
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts1F25T81ELECT DIMElectronic Dimming25
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts2F25T81ELECT DIMElectronic Dimming49
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts3F25T81ELECT DIMElectronic Dimming76
3 foot Fluorescent Rapid Start T8 (25W) Electronic Ballasts4F25T81ELECT DIMElectronic Dimming96
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)1F32T8/30ES1ELECT NOElectronic Normal Output29
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)2F32T8/30ES1ELECT NOElectronic Normal Output54
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)3F32T8/30ES1ELECT NOElectronic Normal Output79
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)4F32T8/30ES1ELECT NOElectronic Normal Output104
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)1F32T8/30ES1ELECT ROElectronic Reduced Output27
TypeLamps - NumberLamps ­ DesignationBallasts NumberBallasts ­ DesignationBallasts ­ DescriptionSystem Watts
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)2F32T8/30ES1ELECT ROElectronic Reduced Output48
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)3F32T8/30ES1ELECT ROElectronic Reduced Output70
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)4F32T8/30ES1ELECT ROElectronic Reduced Output91
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)1F32T8/30ES1ELECT NO EEEE Normal Output33
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)2F32T8/30ES1ELECT NO EEEnergy efficiency Normal Output52
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)3F32T8/30ES1ELECT NO EEEnergy efficiency Normal Output77
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)4F32T8/30ES1ELECT NO EEEnergy efficiency Normal Output101
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)1F32T8/30ES1ELECT RO EEEE Reduced Output28
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)2F32T8/30ES1ELECT RO EEEE Reduced Output45
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)3F32T8/30ES1ELECT RO EEEE Reduced Output66
4 foot Fluorescent Instant Start T8 (“Energy Saving” 30W)4F32T8/30ES1ELECT RO EEEE Reduced Output88
4 foot Fluorescent Rapid Start T8 (32W)1F32T81ELECT NOElectronic Normal Output32
4 foot Fluorescent Rapid Start T8 (32W)2F32T81ELECT NOElectronic Normal Output62
4 foot Fluorescent Rapid Start T8 (32W)3F32T81ELECT NOElectronic Normal Output93
4 foot Fluorescent Rapid Start T8 (32W)4F32T81ELECT NOElectronic Normal Output114
4 foot Fluorescent Rapid Start T8 (32W)1F32T81EE NOEE Normal Output35
TypeLamps - NumberLamps ­ DesignationBallasts NumberBallasts ­ DesignationBallasts ­ DescriptionSystem Watts
4 foot Fluorescent Rapid Start T8 (32W)2F32T81EE NOEE Normal Output55
4 foot Fluorescent Rapid Start T8 (32W)3F32T81EE NOEE Normal Output82
4 foot Fluorescent Rapid Start T8 (32W)4F32T81EE NOEE Normal Output107
4 foot Fluorescent Rapid Start T8 (32W)1F32T81ELECT ROElectronic Reduced Output29
4 foot Fluorescent Rapid Start T8 (32W)2F32T81ELECT ROElectronic Reduced Output51
4 foot Fluorescent Rapid Start T8 (32W)3F32T81ELECT ROElectronic Reduced Output76
4 foot Fluorescent Rapid Start T8 (32W)4F32T81ELECT ROElectronic Reduced Output98
4 foot Fluorescent Rapid Start T8 (32W)2F32T81ELECT HOElectronic High Output77
4 foot Fluorescent Rapid Start T8 (32W)3F32T81ELECT HOElectronic High Output112
4 foot Fluorescent Rapid Start T8 (32W)1F32T81EE ROEE Reduced Output30
4 foot Fluorescent Rapid Start T8 (32W)2F32T81EE ROEE Reduced Output48
4 foot Fluorescent Rapid Start T8 (32W)3F32T81EE ROEE Reduced Output73
4 foot Fluorescent Rapid Start T8 (32W)4F32T81EE ROEE Reduced Output96
4 foot Fluorescent Rapid Start T8 (32W)2F32T81ELECT TLElectronic Two Level (50 & 100%)65
4 foot Fluorescent Rapid Start T8 (32W)1F32T81ELECT DIM1Electronic Dimming35
4 foot Fluorescent Rapid Start T8 (32W)2F32T81ELECT DIM1Electronic Dimming68
4 foot Fluorescent Rapid Start T8 (32W)3F32T81ELECT DIM1Electronic Dimming102
4 foot Fluorescent Rapid Start T8 (32W)1F32T81ELECT DIM2Electronic Dimming33
4 foot Fluorescent Rapid Start T8 (32W)2F32T81ELECT DIM2Electronic Dimming64

p.616Appendix NA8 –Luminaire Powerp.617

p.6172025 Nonresidential Appendices

p.617Appendix NA8 –Luminaire Powerp.618

p.6182025 Nonresidential Appendices

p.618DIM2

p.618Dimming

p.618Appendix NA8 –Luminaire Powerp.619

p.6192025 Nonresidential Appendices

Figure on PDF page 619
Text in this figure

RO = ballast factor 70 to 85% NO = ballast factor 85 to 100% HO = ballast factor >100%

Type

Lamps

- Number

Lamps - Designation

Ballasts Number

Ballasts - Designation

Ballasts - Description

System

Watts 4 foot Fluorescent Rapid Start T8 (32W)

3 F32T8 1 ELECT

DIM2

Electronic

Dimming

93

4 foot Fluorescent Rapid Start T8 (32W)

4 F32T8 1 ELECT

DIM2

Electronic

Dimming

116

5 foot Fluorescent Rapid Start T8 (40W)

1 F40T8 1 ELECT Electronic 46

5 foot Fluorescent Rapid Start T8 (40W)

2 F40T8 1 ELECT Electronic 79

5 foot Fluorescent Rapid Start T8 (40W)

3 F40T8 1 ELECT Electronic 112

p.619 Needs alt text review
TypeLamps - NumberLamps - DesignationBallasts NumberBallasts - DesignationBallasts - DescriptionSystem Watts
4 foot Fluorescent Rapid Start T8 (32W)3F32T81ELECT DIM2Electronic Dimming93
4 foot Fluorescent Rapid Start T8 (32W)4F32T81ELECT DIM2Electronic Dimming116
5 foot Fluorescent Rapid Start T8 (40W)1F40T81ELECTElectronic46
5 foot Fluorescent Rapid Start T8 (40W)2F40T81ELECTElectronic79
5 foot Fluorescent Rapid Start T8 (40W)3F40T81ELECTElectronic112

p.619Appendix NA8 –Luminaire Powerp.620

p.6202025 Nonresidential Appendices

Table NA8-4 – Fluorescent RapidStart HighOutput (HO)T8, 8 ft
TypeLamps ­ NumberLamps ­ DesignationBallasts - NumberBallasts ­ DesignationBallasts ­ DescriptionSystem Watts
8 foot Fluorescent Rapid Start T8 High Output (86W)1F96T8/HO1ELECTElectronic88
8 foot Fluorescent Rapid Start T8 High Output (86W)2F96T8/HO1ELECTElectronic160

p.620HO = ballast factor >100%

p.620Appendix NA8 –Luminaire Powerp.621

p.6212025 Nonresidential Appendices

Table NA8-5 – HighIntensityDischarge
TypeLamps - NumberLamps ­ DesignationBallasts NumberBallasts ­ DesignationBallasts ­ DescriptionSystem WattsComment
Metal Halide1M35/391MAG STDMag. Stand.58-
Metal Halide1M35/391ELECTElectronic44-
Metal Halide1M501MAG STDMag. Stand.67-
Metal Halide1M501ELECTElectronic58-
Metal Halide1M701MAG STDMag. Stand.95-
Metal Halide1M701ELECTElectronic86-
Metal Halide1M1001MAG STDMag. Stand.130-
Metal Halide1M1001ELECTElectronic110-
Metal Halide1M1501MAG STDMag. Stand.185-
Metal Halide1M1501ELECTElectronic168-
Metal Halide1M1751MAG STDMag. Stand.208-
Metal Halide1M1751ELECTElectronic194-
Metal Halide1M2001MAG STDMag. Stand.232-
Metal Halide1M2501MAG STDMag. Stand.295-
Metal Halide1M2501ELECTElectronic269-
Metal Halide1M3201MAG STDMag. Stand.368-
Metal Halide1M3201ELECTElectronic343-
Metal Halide1M3601MAG STDMag. Stand.422-
Metal Halide1M4001MAG STDMag. Stand.452-
Metal Halide1M4001ELECTElectronic430-
Metal Halide1M4501MAG STDMag. Stand.508-
Metal Halide1M7501MAG STDMag. Stand.818-
Metal Halide1M10001MAG STDMag. Stand.1080-
Metal Halide1M15001MAG STDMag. Stand.1605-
High Pressure Sodium1S351MAG STDMag. Stand.47-
High Pressure Sodium1S501MAG STDMag. Stand.66-
High Pressure Sodium1S701MAG STDMag. Stand.91-
High Pressure Sodium1S1001MAG STDMag. Stand.128-
High Pressure Sodium1S1501MAG STDMag. Stand.188-
High Pressure Sodium1S2001MAG STDMag. Stand.230-
High Pressure Sodium1S2501MAG STDMag. Stand.295-
High Pressure Sodium1S4001MAG STDMag. Stand.464-
High Pressure Sodium1S10001MAG STDMag. Stand.1100-

p.621Appendix NA8 –Luminaire Powerp.622

p.6222025 Nonresidential Appendices

Table NA8-6 PAR36 (Shall NOT–12 Volt apply to trackTungsten Halogen lighting Lamps systems)IncludingMR16, Bi-pin,AR70,AR111,
TypeLamps ­ NumberLamps ­ DesignationBallasts - NumberBallasts ­ DesignationBallasts ­ DescriptionSystem WattsComment
High Pressure Sodium120 watt lamp1ELECTElectronic Power Supply23-
High Pressure Sodium125 watt lamp1ELECTElectronic Power Supply28-
High Pressure Sodium135 watt lamp1ELECTElectronic Power Supply38-
High Pressure Sodium137 watt lamp1ELECTElectronic Power Supply41-
High Pressure Sodium142 watt lamp1ELECTElectronic Power Supply45-
High Pressure Sodium150 watt lamp1ELECTElectronic Power Supply54-
High Pressure Sodium165 watt lamp1ELECTElectronic Power Supply69-
High Pressure Sodium171 watt lamp1ELECTElectronic Power Supply75-
High Pressure Sodium175 watt lamp1ELECTElectronic Power Supply80-
High Pressure Sodium120 watt lamp1MAGMag. Transformer24-
High Pressure Sodium125 watt lamp1MAGMag. Transformer29-
High Pressure Sodium135 watt lamp1MAGMag. Transformer39-
High Pressure Sodium137 watt lamp1MAGMag. Transformer42-

p.622Appendix NA8 –Luminaire Power