NA7.7.1 Lighting Control Systems Installed to Comply with Section 110.9(b)

p.572Indoor Lighting Controls Installation Verifications

Figure on PDF page 572
p.572 Needs alt text review

p.572NA7.7.1 Lighting Control Systems Installed to Comply with Section 110.9(b)

p.572NA7.7.1.1 Installation Inspection

p.572If a lighting control required by Title 24, Part 6 is a field assembled system consisting of two or more components, verify the system components meet all of the requirements for each lighting control type, in accordance with Section 110.9, On the approved installation compliance form, identify, list, and verify each type of lighting control system as follows:

p.572(a) Separately identify and list each type of lighting control system. When there are

p.572identical lighting control systems in a single building, identical lighting control system may be listed together.

p.572(b) Identify and list all requirements for the type of self-contained lighting control

p.572device for which the lighting control system is installed to function as, in accordance with Section 110.9 and in accordance with the Title 20 Appliance Efficiency Regulations.

p.572(c) Verify the lighting control system complies with all of the applicable requirement as

p.572listed.

p.572(d) If the lighting control system does not meet all applicable requirements, the

p.572installation fails.

p.572Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.573

p.5732025 Nonresidential Appendices NA7.7.2 Energy Management Control System (EMCS) Installed in Accordance with