NA7.7.2.1 Installation Inspection

p.5732025 Nonresidential Appendices NA7.7.2 Energy Management Control System (EMCS) Installed in Accordance with

p.573Section 130.0(e)

p.573NA7.7.2.1 Installation Inspection

p.573(a) The EMCS shall be separately tested for each respective lighting control system

p.573for which it is installed to function as.

p.573(b) List and verify functional compliance with all applicable requirements in

p.573accordance with applicable Sections 110.9, 130.1, 130.2 and Section 160.5.

p.573(c) If applicable, list and verify functional compliance with all applicable requirements

p.573for all applications for which the EMCS is installed to function as, in accordance with appliable Section 140.6 and 170.2(e)2 thru 4.

p.573(d) If applicable, list and verify functional compliance with all applicable requirements

p.573for all applications for which the EMCS is installed to function as, in accordance with applicable Section 140.7 and 170.2(e)6.

p.573(e) If applicable, list and verify functional compliance with all applicable requirements

p.573for all applications for which the EMCS is installed to function as, in accordance with applicable Section 150(k) and 160.5(a).

p.573NA7.7.3 RESERVED

p.573NA7.7.4 Interlocked Lighting Systems Serving an Area in Accordance with Section

p.573140.6(a)1 and 170.2(e)2A

p.573NA7.7.4.1 Installation Inspection

p.573Verify and document the following:

p.573(a) The space qualifies only as one or more the following types: Auditorium,

p.573convention center, conference room, multipurpose room, or theater, in accordance with the definitions of those space types in Section 100.1.

p.573(b) There are no more than two interlocked lighting systems serving the space.

p.573(c) The two lighting systems are interlocked with a non-programmable double throw

p.573switch to prevent simultaneous operation, in accordance with applicable Section 140.6(a)1 and 170.2(e)2A.

p.573(d) If all of the above items are not true, the installation fails, and all connected lighting

p.573in the space shall be counted as part of the total installed lighting power.

p.573NA7.7.5 Lighting Controls Installed to Earn a Power Adjustment Factor (PAF) in

p.573Accordance with Section 140.6(a)2 and 170.2(e)2B.

p.573NA7.7.5.1 Construction Inspection for all PAFs except Institutional Tuning

p.573Verify and document the following:

p.573Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes