Appendix JA9 – Qualification Requirements for Low Leakage Air-Handling Units

Figure on PDF page 245
Text in this figure

Joint Appendix JA9

p.245 Needs alt text review

p.245Appendix JA9 – Qualification Requirements for Low Leakage Air-Handling Units

p.245JA9.1 Purpose and Scope

p.245Joint Appendix JA9 provides the qualification requirements for air-handling units to meet the requirements for low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Title 24, Part 6, Sections 150.1(b), 140.1, and 170.1. Joint Appendix JA9 is applicable to air-handling units intended for installation in ducted forced-air space conditioning systems. Joint Appendix JA9 is applicable to air-handling units that are rated by the manufacturer to move less than 3,000 cfm (1400 L/s) of air.

p.245Air-handling unit equipment types include:

p.245(a) furnaces

p.245(b) heat pumps

p.245(c) air conditioners

p.245Joint Appendix JA9 does not apply to coil boxes, filter boxes, or other duct system components that are not an integral part of the air-handling unit cabinet or enclosure certified by the manufacturer.

p.245Joint Appendix JA9 does not apply to ducts, plenums, or other field-constructed components.

p.245JA9.2 Qualification Requirements

p.245To qualify as a low leakage air-handling unit for use for compliance with applicable performance compliance credits, the air-handling unit shall be certified to the Energy Commission according to the following requirements:

p.245JA9.2.1 Method of Test

p.245The air-handling unit shall be tested in accordance with the requirements given in ASHRAE Standard 193.

p.245JA9.2.2 Testing Laboratory Requirements

p.245The Air-Handling Unit shall be tested in a laboratory that has demonstrated compliance with ISO Standard 17025, General Criteria for the Competence of Testing and Calibration Laboratories, and is accredited for the ASHRAE Standard 193 test methods. The accreditation body shall be a signatory to the International Laboratory Accreditation Cooperation Mutual Recognition Arrangement (ILAC MRA) www.ilac.org.

p.245Appendix JA9 – Qualification Requirements for Low Leakage Air-Handling Units