p.234JA8.4 Qualification Requirements
p.234The following qualification requirements must be met for the light source to be considered High Luminous Efficacy as specified in Section 150(k).
p.234JA8.4.1 Luminous Efficacy
p.234The light source shall meet the following requirements when measured in accordance with the test method of Section JA8.3.1:
p.234The luminous efficacy of the light source shall be equal to or greater than either the applicable State or federal appliance efficiency standard or 45 lumens/Watt, whichever is higher, when tested at its full light output.
p.234JA8.4.2 Power Factor
p.234The light source shall meet the following requirements when measured in accordance with the test method of Section JA8.3.2:
p.234The light source shall have a power factor equal to or greater than 0.90 when tested at its full light output.
p.234JA8.4.3 Start Time
p.234The light source shall meet the following requirements when measured in accordance with the test method of Section JA8.3.3:
p.234Appendix JA8 – Qualification Requirements for High Luminous Efficacy Light Sourcesp.235
p.235The light source shall have a start time no greater than 0.5 seconds.