RA3.2 Field Verification and Diagnostic Testing of Refrigerant Charge for Air Conditioners and Heat Pumps

p.338RA3.2 Field Verification and Diagnostic Testing of Refrigerant Charge for Air Conditioners and Heat Pumps

p.338RA3.2.1 Purpose and Scope

p.338(a) The procedures in Appendix RA3.2 are for use for residential air-cooled air conditioners

p.338and air-source heat pumps to verify the systems have the required refrigerant charge.

p.338(b) For dwelling units with multiple air conditioners or heat pumps, the procedures shall be

p.338applied to each system separately.

p.338(c) Appendix RA3.2 defines two procedures, the Standard Charge Verification Procedure in

p.338Section RA3.2.2 and the Weigh-in Charging procedure in Section RA3.2.3.

p.338(d) Sections 150.1(c)7 and 150.2(b)1F specify the requirements for minimum system airflow

p.338rates to be verified in conjunction with the refrigerant charge verification.

p.338Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.339

p.3392025 Residential Appendices (e) Failure to follow the manufacturer’s installation and charging instructions may result in

p.339significant refrigeration system faults that may invalidate refrigerant charge and metering device verification results. The installer shall certify that he/she has conformed to the manufacturer’s instructions and specifications for charging the system prior to proceeding with the verification procedures in this appendix.

p.339(f) In the case where the Energy Commission has approved an alternative protocol as

p.339described in RA1, the HVAC Installer and ECC-Rater may choose to perform the alternative refrigerant charge verification procedure.