p.587NA7.11.1 Kitchen Exhaust Systems with Type I Hood Systems
p.587The following acceptance tests apply to commercial kitchen exhaust systems with Type I exhaust hoods. All Type I exhaust hoods used in commercial kitchens shall be tested.
p.587NA7.11.1.1 Construction Inspection
p.587Step 1: Verify exhaust and replacement air systems are installed, power is installed and
p.587control systems such as demand control ventilation are calibrated.
p.587Step 2: For kitchen/dining facilities having total Type 1 and Type II kitchen hood exhaust
p.587airflow rates greater than 5,000 cfm, calculate the maximum allowable exhaust rate for each Type 1 hood as specified by Table 140.9-C.
p.587NA7.11.1.2 Functional Testing at Full Load Conditions
p.587The following acceptance test applies to systems with and without demand control ventilation exhaust systems. These tests shall be conducted at full load conditions.
p.587Step 1: Operate all sources of outdoor air providing replacement air for the hoods.
p.587Step 2: Operate all sources of recirculated air providing conditioning for the space in
p.587which the hoods are located.
p.587Step 3: Operate all appliances under the hoods at operating temperatures.
p.587Step 4: Verify that the thermal plume and smoke is completely captured and contained
p.587within each hood at full load conditions by observing smoke or steam produced by actual cooking operation and/or by visually seeding the thermal plume using devices such as smoke candles or smoke puffers. Smoke bombs shall not be used (note: smoke bombs typically create a large volume of effluent from a point source and do not necessarily confirm whether the cooking effluent is being captured). For some appliances (e.g., broilers, griddles, fryers), actual cooking at the normal production rate is a reliable method of generating smoke). Other appliances that typically generate hot moist air without smoke (e.g., ovens, steamers) need seeding of the thermal plume with artificial smoke to verify capture and containment.
p.587Step 5: Verify that space pressurization is appropriate (e.g., kitchen is slightly negative
p.587relative to adjacent spaces and all doors open/close properly).
p.587Step 6: Verify that each Type 1 hood has an exhaust rate that is below the maximum allowed.
p.587Step 7: Make adjustments as necessary until full capture and containment and adequate
p.587space pressurization are achieved and maximum allowable exhaust rates are not exceeded. Adjustments may include:
p.587(a) Adjust exhaust hood airflow rates.
p.587(b) Add hood side panels.
p.587(c) Add rear seal (back plate).
p.587Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.588
p.5882025 Nonresidential Appendices (d) Increase hood overhang by pushing equipment back.
p.588(e) Relocate supply outlets to improve the capture and containment performance.
p.588Step 8: Measure and record final exhaust airflow rate per Type 1 hood.